In brief
Regulation 20 is the part of SOLAS that treats a vehicle deck as its own fire problem. It has three functional requirements: protect the ship from the fire hazards of vehicle spaces, separate ignition sources from them, and ventilate them adequately.
The 2000 revision set the structure still in use: power ventilation at fixed air-change rates, electrical equipment safe for petrol vapour, a fixed fire detection system tested under normal ventilation, and fixed fire extinction sized for the space. Resolution MSC.550(108), in force 1 January 2026, is the largest change since. It requires both smoke and heat detection on new passenger ships, adds the weather deck to the regulation's scope, and requires video monitoring of vehicle decks on passenger ships.
Who it applies to
- Vehicle spaces, special category spaces and open and closed ro-ro spaces on passenger ships and cargo ships, including PCTCs, ro-ro cargo ships and ro-pax ferries.
- Since 1 January 2026, also weather decks intended for the carriage of vehicles.
- Each paragraph states the ship type and construction date it applies to. Existing ships keep their previous requirements unless a paragraph says otherwise.
What it requires
- 20.3.1
- Ventilation
At least 10 air changes per hour in special category spaces and in closed ro-ro and vehicle spaces of passenger ships carrying more than 36 passengers; 6 per hour on passenger ships carrying no more than 36 passengers and on cargo ships. Since 2017 an air quality control system may justify lower rates, except where 10 changes are required for electrical-equipment reasons and in regulation 20-1 spaces.
- 20.3.2
- Ignition sources
Electrical equipment and wiring must be suitable for an explosive petrol and air mixture. In spaces other than special category spaces below the bulkhead deck, equipment enclosed to prevent the escape of sparks is allowed more than 450 mm above the deck, if ventilation gives at least 10 air changes per hour while vehicles are aboard.
- 20.4.1
- Fixed fire detection
New passenger ships (2026 on): an individually identifiable system giving smoke and heat detection throughout, tested under normal ventilation, with sections matching the deluge sections. New cargo ships (2026 on): an FSS Code system able to detect the onset of fire rapidly, tested under normal ventilation. Existing passenger ships: heat detectors added wherever a smoke detector is fitted, by the first survey on or after 1 January 2028.
- 20.4.1.4
- Weather-deck detection
New passenger ships must have fixed detection over the weather-deck area intended for vehicles, able to detect the onset of fire anywhere on it. Different settings are allowed during loading and at sea to limit false alarms.
- 20.4.3
- Special category spaces
An efficient fire patrol system must be maintained. Manual call points are placed so that no part of the space is more than 20 m from one.
- 20.4.4
- Video monitoring (passenger ships)
Cameras covering the whole space, high enough to see over the loaded vehicles, with immediate playback. Recordings kept for 7 days on ships built from 2026 and 24 hours on existing ships, with each camera mapped to its drencher section. Continuous watching by the crew is not required.
- 20.6.1
- Fixed fire extinction
Sealable vehicle and ro-ro spaces that are not special category spaces carry a fixed gas, high-expansion foam or water-based system to the FSS Code (ships built from 1 July 2014). Spaces that cannot be sealed, and special category spaces, carry a fixed water-based system protecting every deck and vehicle platform. Drainage and stability arrangements must cope with the water it puts on deck (20.6.1.4).
- 20.6.2
- Weather-deck monitors (passenger ships)
A fixed water-based system based on monitors covering weather decks intended for vehicles. On existing passenger ships, by the first survey on or after 1 January 2028, each monitor delivers at least 1,250 L/min unless the Administration accepts less.
- 20.7
- Decision-making signage (new passenger ships)
Photoluminescent section-number signs on the deckhead and bulkheads, matching the section valves and the safety-centre display.
On a vehicle deck
The detection wording is the part a detection buyer should read closely. For new cargo ships, including PCTCs, the 2026 text keeps the performance language: a system 'capable of rapidly detecting the onset of fire', positioned 'taking into account the effects of ventilation', with an overall response time 'to the satisfaction of the Administration'. It does not prescribe a technology, so the flag Administration and the class society decide what meets it.
For passenger ships the text is prescriptive: smoke and heat detection, individually identifiable, sectioned to match the drencher, with video for confirmation. Existing ro-pax ships have until their first survey on or after 1 January 2028 to add heat detection and video, which makes 2026 and 2027 the retrofit window for that fleet.
Regulation 20 sets a minimum. A detection layer that watches each vehicle sits alongside the required system; it does not replace it.
On the timeline
Full timeline →- 1 Jul 2002Revised Chapter II-2 and FSS Code in force
Regulation 20 in its modern form applies to ships built from this date.
Discussed in our articles
57 articles cite SOLAS II-2/20, newest first.
- Can a Missile Strike Set a Car Carrier Alight?Blogs
- What Do France's EV Shipping Guidelines Ask?Blogs
- Can High-Expansion Foam Stop an EV Fire?Technical Articles
- Can a Car Carrier Shut Its Vents Once It Burns?Blogs
- What Did Fremantle Highway's Fire Alarms Show?Technical Articles
- El. Venizelos: Five Days on Garage Deck 3Case Studies
- Can Crews Find the Right Drencher in Smoke?Blogs
- How Often Must a Car-Deck Drencher Be Tested?Blogs
Show all 57 articlesShow fewer
- How Fast Does Smoke Fill a Car Deck?Technical Articles
- Joseph and Clara Smallwood: The Silent AlarmCase Studies
- Can a Car-Deck Fire Travel Through the Ducts?Blogs
- Does a Cold Car Deck Lower EV Fire Risk?Blogs
- Do Beam Smoke Detectors Work on a Car Deck?Technical Articles
- RoRo Fire Protection: EV Fire DetectionBlogs
- Stena Spirit: The Fire Mistaken for a BeltCase Studies
- When Does a Heat Detector Alarm on a Car Deck?Technical Articles
- Corona Seaways: The Key Left in the IgnitionCase Studies
- Are Electric Tugmasters a Deck Fire Risk?Blogs
- Can a Hose Put Out a Car Fire on Deck?Blogs
- Do SOLAS Fire Rules Cover Domestic Ferries?Blogs
- Do Fire Patrols Still Work on a Car Deck?Blogs
- How to Evaluate Fire Detection for a PCTCBlogs
- What Port State Control Checks on DecksBlogs
- Should Car-Deck Fans Stop in an EV Fire?Blogs
- Why Fire Detection Is Difficult on Ro-Ro Vehicle DecksBlogs
- SOLAS II-2/7: Fixed Detection vs IRTechnical Articles
- Fire Detection vs Video Monitoring on Ro-Ro ShipsBlogs
- SOLAS 2026 Video Monitoring: Who Is Watching?Blogs
- SOLAS II-2/20 Checklist for Ro-Ro Ship OperatorsBlogs
- SOLAS II-2/20 Explained: 2026 Ro-Ro Fire RulesBlogs
- Are E-Bikes the Ferry Deck's New Fire Risk?Blogs
- Does Car-Carrier Fire Compliance Arrive in 2027?Blogs
- At What %LEL Should a Car-Deck Gas Alarm Trip?Technical Articles
- Is Fire Detection Off While the Ship Loads?Blogs
- Which Rulebook Governs an EV Fire at Sea?Blogs
- Pearl of Scandinavia: The First EV Fire at SeaCase Studies
- What Does SOLAS II-2/20 Ask of a Car Carrier?Blogs
- Marine-Spec Thermal Cameras on DeckTechnical Articles
- Does a Car in a Container Escape the Rules?Blogs
- Fiber-Optic Linear Heat Detection on RoRoTechnical Articles
- How Fast Can You See a Hydrogen Leak?Technical Articles
- Does a Hydrogen Car Belong on a Car Deck?Blogs
- How Many Alarms Can a Bridge Team Absorb?Technical Articles
- Does EV Accumulation Start on the Quay?Blogs
- Does EV-Ready Tonnage Earn a Premium?Blogs
- Scenario: Ro-Pax EV-Deck MonitoringCase Studies
- Does Deck Ventilation Delay Fire Detection?Technical Articles
- Does an EV Fire Make a Ship Unseaworthy?Blogs
- Does UR E26/E27 Apply to Fire Detection?Technical Articles
- Detection Retrofit: Who Actually Pays?Blogs
- Scenario: A Season of At-Sea Alarm DataCase Studies
- Scenario: Commissioning a Newbuild PCTCCase Studies
- Do Drencher Systems Stop an EV Deck Fire?Blogs
- Is Car-Carrier Fire a Soft Market's Blind Spot?Blogs
- What the 2026 PFOS Foam Ban Means for RoRoBlogs
- Aspirating vs Point Smoke on Vehicle DecksTechnical Articles
- Can Water Suppression Worsen an EV Blast?Blogs
Sources we checked
- IMO — Resolution MSC.99(73), adopted 5 December 2000, in force 1 July 2002: Regulation 20 purpose, ventilation rates (20.3.1.1), electrical equipment (20.3.2), detection (20.4), fire patrol and call points (20.4.3), fixed extinction (20.6). (opens in a new tab)
- IMO — Resolution MSC.338(91), adopted 30 November 2012, in force 1 July 2014: revised 20.6.1.1 fixed extinction options for sealable spaces. (opens in a new tab)
- IMO — Resolution MSC.392(95), adopted 11 June 2015, in force 1 January 2017: air quality control system option, 20.3.1.2.4. (opens in a new tab)
- IMO — Resolution MSC.421(98), adopted 15 June 2017, in force 1 January 2020: new 20.2.1.2 on vehicles carried in other cargo spaces. (opens in a new tab)
- IMO — Resolution MSC.550(108), adopted 23 May 2024, in force 1 January 2026: new title, 20.2.1.3, 20.4.1 to 20.4.1.6, 20.4.4, 20.5, 20.6.2 and 20.7. (opens in a new tab)
These pages are RoRoSAFE’s plain-English summaries, written for orientation and checked against the sources listed. They are not legal advice and do not replace the official text, which prevails. IMO conventions and codes are published by IMO; we link to official and free copies rather than reproducing them.