When Does a Heat Detector Alarm on a Car Deck?

Once the fire is real. Ceiling gas must reach 54 °C: about 330 kW of fire on a 2.5 m deck, 1.6 MW on a 6.5 m one. A venting battery gives neither.
Only once there is a real fire. Under the FSS Code a ceiling heat detector trips between 54 and 78 °C. On a 2.5 m car deck, the fire must reach about 330 kW before the ceiling gas at the worst-placed point gets to 54 °C; on a 6.5 m deck, about 1.6 MW. A venting battery produces neither.
This matters more from 2026. The amended SOLAS II-2/20 requires smoke and heat detection throughout the vehicle decks of new ro-pax ships, and existing ro-pax ships must add heat detection by their first survey on or after 1 January 2028. Heat is also the one detection function that may not be switched off while vehicles are loading. Owners are buying a great deal of heat detection, so it is worth knowing exactly what it will and will not see.
What does the FSS Code require of a heat detector?
A fixed trip point inside a narrow band, and a minimum density on the deckhead. As amended by resolution MSC.555(108), in force 1 January 2026, FSS Code Chapter 9 paragraph 2.3.1.3 requires heat and linear heat detectors to operate before the temperature exceeds 78 °C but not until it exceeds 54 °C, when heated at less than 1 °C per minute, tested to EN 54:2001 and IEC 60092-504. At faster rates of rise the Administration sets the limits. Linear heat detectors on ships built from 2026 are tested to EN 54-22:2015.
- Heat detectors: at most 37 m² of floor each, 9 m apart and 4.5 m from a bulkhead (Table 9.1).
- Smoke detectors: 74 m², 11 m apart, 5.5 m from a bulkhead. Combined smoke and heat heads: 74 m², 9 m, 4.5 m.
- Linear heat cables: no more than 9.0 m apart and 4.5 m from a bulkhead.
Point detectors are sold in EN 54-5 classes. Class A1 responds between 54 and 65 °C and class A2 between 54 and 70 °C, both inside the FSS window; class B responds between 69 and 85 °C, so only part of its band fits under the 78 °C limit. A rate-of-rise variant can respond earlier to a fast-growing fire, within limits the Administration accepts.
Where do the 2026 heat detectors go?
On new ro-pax ships, throughout the space; on existing ones, at the smoke detector positions. Regulation 20.4.1.1, as adopted by MSC.550(108), requires an individually identifiable system giving smoke and heat detection throughout the vehicle, special category and ro-ro spaces of passenger ships built from 2026, and accepts linear heat detection for the heat function. For passenger ships built before 2026, paragraph 20.4.1.6 says heat detectors 'shall comply with the spacing and coverage area requirements as applicable for smoke detectors' and are 'only required where there is already a smoke detector'.
Read literally, that puts a heat head at each existing smoke head, up to 11 m apart, rather than at the 9 m heat-only spacing. New cargo ships, including car carriers, get no explicit heat requirement: the 2026 text asks for an FSS Code system able to detect the onset of fire rapidly. And on new ro-pax ships, FSS Code paragraph 2.5.1.4 lets the smoke function be disconnected during loading but forbids disconnecting heat detection or manual call points.
How big must a fire be before the ceiling reaches 54 °C?
Hundreds of kilowatts on a low deck, megawatts on a tall one. Alpert's ceiling-jet correlations estimate the gas temperature under a flat ceiling from the fire's heat release Q (kW), the height H from fire to ceiling (m) and the radial distance r (m): directly above the fire the temperature rise is 16.9 Q^(2/3) / H^(5/3), and further out it is 5.38 (Q/r)^(2/3) / H. The figures below assume 20 °C deck air, a fire seated 0.3 m above the deck, steady burning, an open ceiling and a detector that reads the gas temperature instantly.
- 2.5 m deck: about 20 kW if the fire is directly under a detector, 230 kW at 4.5 m, 330 kW at 6.4 m (the centre of a 9 m grid) and 400 kW at 7.8 m (the centre of an 11 m grid).
- 4.5 m deck: about 100 kW, 620 kW, 870 kW and 1.06 MW at the same four distances.
- 6.5 m deck: about 270 kW, 1.10 MW, 1.56 MW and 1.91 MW.
- For a detector that trips at 65 °C, the top of class A1, the fire must be about half as large again: roughly 500 kW at the centre of a 9 m grid on a 2.5 m deck and 2.4 MW on a 6.5 m deck.
How does that compare with a burning car?
On a tall deck, the detector at the worst point waits for a fire that is already a substantial fraction of a car's peak. A 2013 analysis of published single-vehicle fire tests in Fire Science Reviews put the mean peak heat release at about 3.5 MW for small cars and 6.8 MW for medium cars, with light-car tests peaking between roughly 1.5 and 8.9 MW some 12 to 33 minutes after ignition. On that basis the worst-placed detector on a 6.5 m deck alarms when the fire is roughly a quarter to a half of its eventual peak. On a 2.5 m deck it alarms at a tenth of the peak or less.
Where the fire starts matters too. A 2025 systematic review of passenger-car fire experiments found that fires starting underneath the car reached higher peaks sooner than fires starting elsewhere. A battery pack sits under the floor.
What does a failing battery do before a heat detector can see it?
It vents gas, not heat. In the stages before ignition a lithium-ion pack heats internally and releases electrolyte vapour and runaway gas, but the heat reaching the deck air is small until that gas ignites. The earliest release is also heavy, carbonate solvent vapour being three to four times as dense as air, so it tends to stay low rather than rise to the deckhead. A ceiling heat detector is therefore blind to the venting stage by design. It responds only once there is flaming combustion of a few hundred kilowatts or more.
A hot deckhead adds a second constraint. Steel under a sunlit weather deck has been measured at 60 to 70 °C in tropical waters, above the 50 °C maximum application temperature of an A1 detector. A detector rated for that environment trips later, at the top of the FSS window rather than near 54 °C.
What should owners take from this?
Treat heat detection as reliable fire confirmation, not early warning.
- Its value is robustness: exhaust haze does not trip it, which is why the 2026 rules keep it switched on during loading.
- On tall decks, the code maximum spacing leaves the worst point needing well over a megawatt. Tighter spacing, or linear heat cables run over each lane, shortens that distance.
- For existing ro-pax ships adding heat heads at smoke positions before 2028, check the worst-point distance against the deck height, not just the head count.
- Choose the detector class against the deckhead's measured temperature in service, not the design ambient.
- Cover the venting stage separately, close to the vehicles, where the gas and heat start.
How RoRoSAFE helps
A ceiling heat detector confirms a car-deck fire once it reaches a few hundred kilowatts or more; it cannot see a battery venting beneath it. RoRoSAFE watches each parked vehicle with infrared thermal and battery-vent gas sensing, alerts before visible smoke, and sends tiered bridge and shore alerts naming the deck and bay. It complements the SOLAS smoke and heat detection the 2026 rules require and replaces neither.
Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access
Sources
- 1. IMO — Resolution MSC.555(108), adopted 23 May 2024, in force 1 January 2026: FSS Code Chapter 9 paragraphs 2.3.1.3 (54–78 °C, EN 54:2001 and IEC 60092-504), 2.3.1.5 (EN 54-22:2015), 2.4.2.2 and Table 9.1 (spacing), 2.4.2.2.2 (linear heat cables) and 2.5.1.4 (disconnection during loading).
- 2. IMO — Resolution MSC.550(108), adopted 23 May 2024, in force 1 January 2026: SOLAS II-2/20.2.1.3, 20.4.1.1, 20.4.1.5 and 20.4.1.6 (existing passenger ships by the first survey on or after 1 January 2028).
- 3. EN 54-5 heat detector classes (A1 54–65 °C, A2 54–70 °C, B 69–85 °C static response; A1 maximum application temperature 50 °C), as reproduced in distributor and manufacturer declarations of performance.
- 4. R. L. Alpert, 'Calculation of response time of ceiling-mounted fire detectors', Fire Technology 8 (1972), ceiling-jet temperature correlations; and Alpert's 2011 review of the same correlations (Fire Safety Science 10).
- 5. 'Distribution analysis of the fire severity characteristics of single passenger road vehicles using heat release rate data', Fire Science Reviews 2013, 2:5 (DOI 10.1186/2193-0414-2-5): mean peak heat release by vehicle class and per-test peaks and times to peak.
- 6. Systematic review of passenger-car fire experiments, Fire Technology (2025), DOI 10.1007/s10694-025-01701-5: underbody-origin fires reach higher, earlier peaks.
- 7. RoRoSAFE engineering calculation: Alpert correlations at 20 °C ambient, fire seated 0.3 m above the deck, temperature rises of 34 K (54 °C) and 45 K (65 °C), deck heights of 2.5, 4.5 and 6.5 m, and radial distances of 0, 4.5, 6.4 and 7.8 m. Steady state; detector thermal lag, ventilation and obstruction not modelled.
- 8. Solvent vapour density (three to four times air) and tropical deckhead temperatures of 60–70 °C (Fire Research Note 633, 1966), as summarised in RoRoSAFE's 'Does a Battery Vent Plume Reach the Ceiling?'.
Questions, answered
At what temperature does a marine heat detector alarm?+
Under FSS Code Chapter 9, as amended for 2026, a heat or linear heat detector must operate before the temperature exceeds 78 °C but not until it exceeds 54 °C, when heated slowly. EN 54-5 class A1 detectors respond between 54 and 65 °C and class A2 between 54 and 70 °C, both within that window.
How far apart are heat detectors on a vehicle deck?+
FSS Code Table 9.1 allows each heat detector up to 37 m² of floor, 9 m from the next and 4.5 m from a bulkhead. Smoke detectors may be 11 m apart. For existing ro-pax ships adding heat detection by 2028, SOLAS II-2/20.4.1.6 ties the heat detectors to the existing smoke detector spacing.
Can a heat detector catch an EV battery fire early?+
No. Before ignition a failing battery mainly releases gas, and the earliest vapour is heavy and stays low. A ceiling heat detector responds only when a flaming fire heats the ceiling gas past its trip point, which on a car deck takes a fire of a few hundred kilowatts to over a megawatt depending on deck height.
Why can't heat detection be switched off during loading?+
Because it is the function vehicle exhaust cannot fool. For new ro-pax ships, FSS Code paragraph 2.5.1.4 lets the smoke function in ro-ro and special category spaces be disconnected for loading and unloading, with automatic reset, but forbids disconnecting heat detection or manual call points. Heat detection is the fire watch that stays on.
Continue the thread
Fiber-Optic Linear Heat Detection on RoRo
SOLAS has required heat detection on new ro-pax vehicle decks since 1 January 2026 — and a line-type detector answers that with a cable, not a grid.

Does a Battery Vent Plume Reach the Ceiling?
Often not at first. Early electrolyte vapour is 2–3× denser than air and stays low; only the hot runaway gas rises fast enough for ceiling detectors.
Aspirating vs Point Smoke on Vehicle Decks
Point detectors alarm only once diluted smoke reaches the deckhead; aspirating (ASD) systems sample air continuously and trip far earlier.

The Four Stages of Li-Ion Thermal Runaway
Li-ion runaway moves from SEI breakdown near 80–120 °C through venting to fire. Useful detection works in the venting window, before smoke and flame.

Does Deck Ventilation Delay Fire Detection?
Yes. SOLAS II-2/20 mandates continuous ventilation on closed vehicle decks, and that airflow dilutes smoke and off-gas before detectors see it.

Does the 2026 SOLAS Rule Reach Old Ships?
Only if it is a passenger ship. MSC.550(108) catches existing ro-pax at the first survey on or after 1 Jan 2028; an existing car carrier is not named.

PCC vs PCTC: How Detection Differs
A PCC's fixed 1.7 m car decks and a PCTC's liftable decks up to 6.7 m pose different detection problems: distance, airflow and cargo that blocks.