Code

FSS Code

International Code for Fire Safety Systems (Fire Safety Systems Code)

In forceIMO Maritime Safety CommitteeChecked 18 October 2026

The FSS Code holds the engineering specifications behind SOLAS II-2: fixed gas, water-spray and detection systems. Mandatory since 1 July 2002.

In brief

The FSS Code is where SOLAS keeps its engineering numbers. Chapter II-2 says a space needs a fixed fire-extinguishing system or a fixed detection system; the FSS Code says how much gas, what water density and what detector performance.

It was adopted on 5 December 2000 by resolution MSC.98(73) and became mandatory on 1 July 2002, when the revised Chapter II-2 entered into force. It has 15 original chapters, from fire extinguishers to inert gas systems.

Who it applies to

  • Every fire safety system that SOLAS Chapter II-2 requires, on the ships that chapter applies to.
  • Individual chapters and paragraphs carry their own construction-date applicability.

What it requires

Chapter 5
Fixed gas fire-extinguishing systems

For vehicle and ro-ro spaces that are not special category spaces, carbon dioxide sufficient for at least 45% of the gross volume of the largest sealable space, with at least two thirds introduced within 10 minutes (2.2.1.2, from 1 July 2014). General cargo spaces: 30%.

Chapter 7
Fixed water-spraying and water-mist systems

Water-based systems for ro-ro, vehicle and special category spaces are approved under IMO guidelines (2.4, MSC.1/Circ.1430). Since 2026, 2.5 specifies weather-deck monitors on new ro-pax ships.

Chapter 9
Fixed fire detection and fire alarm systems

Power supplies, detector performance (heat detectors operate between 54 °C and 78 °C), spacing (Table 9.1), sectioning and alarm presentation. Applies to ships built from 1 July 2012 unless stated otherwise.

Chapter 10
Sample extraction smoke detection

Aspirating systems. SOLAS II-2/20 allows them as an alternative in closed spaces, but not in open ro-ro spaces, open vehicle spaces or special category spaces.

On a vehicle deck

Most of what a class surveyor checks on a vehicle deck is FSS Code arithmetic: the CO₂ quantity against the largest sealable hold, drencher density against deck height, and detector spacing against the deckhead area.

Detector spacing sets the minimum density of ceiling detectors, not where a fire starts. On a loaded car deck the source is often below the vehicles, several metres from the nearest detector, which is why detection close to each vehicle can be added alongside the code-compliant system.

On the timeline

Full timeline →
  1. 5 Dec 2000
    Chapter II-2 rewritten; FSS Code adopted

    Resolutions MSC.99(73) and MSC.98(73) adopt a completely revised fire chapter, including Regulation 20 for vehicle spaces, and move the engineering specifications into the FSS Code.

  2. 1 Jul 2014
    Fixed extinction rules revised

    MSC.338(91) and MSC.339(91) enter into force: sealable vehicle spaces may use gas, high-expansion foam or water-based systems, and the 45% CO₂ rule moves into the FSS Code.

Discussed in our articles

61 articles cite FSS Code, newest first.

Show all 61 articles

Sources we checked

  1. IMO — Resolution MSC.98(73), adopted 5 December 2000: FSS Code, effective 1 July 2002; table of contents (Chapters 1–15); Chapter 5 2.2.1.1, 30% for cargo spaces. (opens in a new tab)
  2. IMO — Resolution MSC.339(91), adopted 30 November 2012: new Chapter 5 2.2.1.2 (45% for vehicle and ro-ro spaces, two thirds within 10 minutes); Chapter 7 2.4. (opens in a new tab)
  3. IMO — Resolution MSC.555(108), adopted 23 May 2024, in force 1 January 2026: Chapter 7 2.5; Chapter 9 1.1, 2.3.1.3, Table 9.1. (opens in a new tab)
  4. IMO — Resolution MSC.99(73): SOLAS II-2/20.4.2, sample extraction systems not accepted in open ro-ro, open vehicle or special category spaces. (opens in a new tab)

These pages are RoRoSAFE’s plain-English summaries, written for orientation and checked against the sources listed. They are not legal advice and do not replace the official text, which prevails. IMO conventions and codes are published by IMO; we link to official and free copies rather than reproducing them.

Detection that sits alongside the rules

A one-deck pilot, installed alongside the berth with no drydock. It complements the SOLAS detection and suppression on board and replaces neither.

Request a pilot