Can a Car-Deck Fire Travel Through the Ducts?

By Vignesh Durai · · 4 min read

Yes. Ducts carry smoke, heat and flammable vapour out of a car deck, and a seized or damaged fire damper turns them into a route into other spaces.

Yes. A car deck is ventilated through ducts that cross fire boundaries, and the fire damper in each duct is the only thing standing between the deck and the next space. When a damper is seized, left open or the duct itself is damaged, smoke, heat and flammable vapour can travel through it. Investigations into Britannia Seaways, Corona Seaways and Höegh Xiamen each traced part of the outcome to ventilation that did not close as designed.

This is a different question from whether to stop the fans in an EV fire. That decision only works if the hardware behind it holds. Here the subject is the hardware itself: the ducts, dampers and closures, and how they fail.

How is a car deck's ventilation meant to contain a fire?

By closing it off from outside the space and keeping every duct inside the fire boundary it crosses. SOLAS regulation II-2/20 requires vehicle and ro-ro spaces to be ventilated continuously while vehicles are aboard, at 6 air changes an hour on cargo ships and 10 on passenger ships. It also requires arrangements to shut the system down rapidly and close it effectively from outside the space in a fire. Regulation II-2/9.7 governs the ducts. They must be steel or equivalent. Where a duct of 0.075 m² or more passes through an A-class division, it needs an automatic, fail-safe fire damper. An IMO unified interpretation adds that a duct serving one ro-ro space and passing through another, without serving it, must be insulated to A-30 there, unless dampers and sleeves are fitted instead.

0.075 m²
Duct size above which an A-class penetration needs an automatic fire damper (SOLAS II-2/9.7)
~5 m²
Gaps left by closed louvres on Corona Seaways (MAIB 17/2014)
Quarterly / annual
Fire damper tests for local and remote operation under MSC.1/Circ.1432

Where have ducts and closures let a fire through?

In at least three investigated ro-ro casualties, each failing in a different way. On Britannia Seaways in 2013, a flatrack sliding in heavy weather damaged a ventilation duct on the weather deck. Petrol and seawater ran down it into an electrical store under the forecastle. When the rising water shorted a switchboard, the petrol vapour exploded. The blast blew out two watertight doors and took down the ship's integrated machinery control system, according to the Danish investigation board. On Corona Seaways the same year, the crew believed the deck louvres were shut. Locking them needed two people and a turn of the spindle past the apparent closed point. Trials afterwards found gaps of about 1.5 cm between the louvres, roughly 5 m² of opening in all. The UK MAIB judged that this fed the fire, and the first CO₂ release delivered about 9 of the 19.8 tonnes needed.

Höegh Xiamen in 2020 is the most expensive example. The NTSB found the dampers for decks 7 and 8 were ineffective or not adequately secured. The fire kept its supply of air and the CO₂ release did not work. The ship and her cargo were lost. In none of these cases did the duct start the fire. In each, it decided how far the fire, its fuel or the extinguishing gas got.

A damper that looks closed and a damper that is closed are different things, and the difference only shows during a fire. Corona Seaways' louvres and Höegh Xiamen's dampers both passed for shut until the CO₂ went in.

What changes when the cargo is electric?

What travels through the duct changes. A failing lithium-ion pack vents flammable gas, including hydrogen, carbon monoxide and electrolyte vapour, before it burns. IUMI's 2025 update to its EV carriage guidance warns that the risk can shift from fire to explosion where those gases collect. A duct that carries vent gas out of a car deck delivers it to the fan room or whatever space the duct reaches. If that space holds switchboards, motors or starters, it has the same ignition sources that lit the petrol vapour in Britannia Seaways' electrical store. Closing the ventilation remains the right first move. It also means a sealed deck holds vent gas, so how and where the space is later reopened matters more with an EV cargo than with petrol cars alone.

How do dampers fail, and how would you know?

Quietly, through corrosion, seized linkages and worn seals, and often without failing the test. IMO's maintenance guidelines, MSC.1/Circ.1432, call for every fire damper to be tested for local operation quarterly. Remote operation should be tested annually, along with any ventilation controls interconnected with the fire-protection systems. Port state control inspectors cite fire dampers among the most common fire-safety deficiencies (code 07115). The recurring defects are dampers that do not fully close or seal, seized or broken closing wires, inoperative remote controls, hardened or missing gaskets, and corroded or perforated flaps. Some dampers pass a functional test but fail a visual inspection because the corrosion and damaged seals are hidden. A damper on a car deck also sees salt air, exhaust and wash water that most dampers ashore never meet.

What should owners and masters check?

  • Test dampers and louvres closed, not just moved, and check the seal by eye; a closure that needs a two-person procedure should be drilled as one.
  • Walk every duct that serves a vehicle deck through to where it ends, and list what is in that space; an electrical room at the end of a car-deck exhaust is a vent-gas ignition point.
  • Inspect duct runs and cowls on weather decks after heavy weather, since cargo shifting in a seaway is what breached the duct on Britannia Seaways.
  • Put damper and louvre closure positions on the fire plan and the CO₂ release checklist, with a positive confirmation step before the gas goes in.
  • Plan reopening with an EV cargo in mind: which fans, which openings, and where the exhaust discharges, so trapped vent gas leaves away from ignition sources and crew.
Conclusion

How RoRoSAFE helps

Ducts decide how far a car-deck fire's heat, gas and smoke travel once it starts. The earlier it is found, the less there is to carry. RoRoSAFE puts an infrared thermal and battery-vent gas cell under each parked vehicle, so a failing pack is flagged before visible smoke. The alert reaches the bridge and shore naming the deck and bay, while closing the ventilation is still a precaution rather than an emergency. It complements the ship's SOLAS detection and suppression.

Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access

Sources

  • 1. IMO — SOLAS chapter II-2, regulation 20.3.1: continuous ventilation of closed vehicle and ro-ro spaces (6 air changes per hour on cargo ships, 10 on passenger ships) and rapid shutdown and effective closure from outside the space in case of fire.
  • 2. IMO — SOLAS chapter II-2, regulation 9.7: ducts of steel or equivalent; automatic fail-safe fire dampers where ducts of 0.075 m² or more penetrate A-class divisions.
  • 3. IMO — MSC.1/Circ.1511/Rev.1, unified interpretations of SOLAS regulations II-2/9 and 13: ducts serving a ro-ro or vehicle space passing through another such space without serving it to be insulated to A-30, unless sleeves and fire dampers to II-2/9.7.3.1 are fitted.
  • 4. IMO — MSC.1/Circ.1432 (as amended by MSC.1/Circ.1516), Revised Guidelines for the Maintenance and Inspection of Fire Protection Systems and Appliances, section 6.3 (quarterly: test all fire dampers for local operation) and section 7.6 (annual: test all fire dampers for remote operation; test ventilation controls interconnected with fire-protection systems), as annexed to Cayman Islands Shipping Notice 01/2014 Rev 2, read in full.
  • 5. Danish Maritime Accident Investigation Board — Marine Accident Report, 'BRITANNIA SEAWAYS — Fire on 16 November 2013', July 2014: ventilation duct damaged by a flatrack; petrol and water entering the electrical store; petrol-vapour explosion ignited by switchboard short circuits, blowing out two watertight doors and disabling the machinery control system.
  • 6. UK Marine Accident Investigation Branch — Report No 17/2014, fire on the main deck of the ro-ro cargo ferry Corona Seaways, 4 December 2013: louvre locking procedure; about 1.5 cm gaps, roughly 5 m² of opening; first CO₂ release about 9 of 19.8 tonnes.
  • 7. NTSB MAR-21/04 — Fire aboard the vehicle carrier Höegh Xiamen, Jacksonville, 4 June 2020: dampers for decks 7 and 8 ineffective or not adequately secured, negating the CO₂ release.
  • 8. IUMI — 'Navigating EV shipping risks: IUMI updates best practice paper', 29 August 2025: risk can shift from fire to explosion where battery gases concentrate; careful consideration of ventilation procedures.
  • 9. IIMS — 'Fire dampers: a critical detention risk in fire safety': fire dampers among the most cited PSC fire-safety deficiencies (deficiency code 07115) and the common defects listed.
Frequently asked

Questions, answered

Can fire spread from a car deck through the ventilation ducts?+

Yes, if the dampers or the ducts fail. SOLAS requires automatic fire dampers where ducts of 0.075 m² or more cross A-class divisions, and a way to close the deck's ventilation from outside. On Britannia Seaways a damaged duct carried petrol into an electrical store, where it exploded. On Höegh Xiamen, ineffective dampers kept the fire supplied with air.

How often should fire dampers on a ship be tested?+

Under IMO's maintenance guidelines, MSC.1/Circ.1432, every fire damper should be tested for local operation quarterly, and for remote operation annually. Ventilation controls interconnected with the fire-protection systems should be tested annually too. A test should confirm the damper closes and seals, since corrosion and worn gaskets can let a damper move freely yet still leak.

Why does an EV cargo make duct integrity more important?+

Because a failing battery vents flammable gas, including hydrogen and carbon monoxide, before it burns. IUMI warns the risk can shift from fire to explosion where that gas collects. A duct that carries vent gas to a fan room or electrical space delivers fuel to ignition sources, which is how petrol vapour exploded in Britannia Seaways' electrical store.

Is this the same as deciding whether to stop the fans?+

No. Stopping the fans is a firefighting decision. It only works if the dampers, louvres and ducts behind it actually seal. Corona Seaways' louvres left about 5 m² of gaps and Höegh Xiamen's dampers were not secured, so the CO₂ in both cases fell short. The hardware has to be tested closed before the decision can work.

Related reading

Continue the thread

FirefightingSafety
Sep 25, 2026 · 5 min read

Should Car-Deck Fans Stop in an EV Fire?

Yes — stopping the fans starves the fire and lets CO₂ work. But a sealed deck also traps battery vent gas, so when and how you reopen it matters as much.

By Vignesh DuraiRead
CasualtyRoRo
Oct 25, 2026 · 6 min read

Britannia Seaways: The Lashings That Let Go

In a 2013 North Sea storm a tank container broke loose on Britannia Seaways, struck sparks off the deck and lit petrol leaking from jerrycans.

By Vignesh DuraiRead
CasualtyRoRo
Oct 17, 2026 · 5 min read

Corona Seaways: The Key Left in the Ignition

In 2013 a used truck's live starter cable set Corona Seaways' deck alight. Unlocked louvres leaked CO₂, and the first release gave 9 of 19.8 tonnes.

By Vignesh DuraiRead
CasualtyNTSB
Jun 17, 2026 · 3 min read

Höegh Xiamen: Anatomy of a Total Loss

The NTSB traced a $40M car-carrier total loss to one used vehicle's improperly disconnected battery — and the oversight that let 2,420 cars load unchecked.

By Vignesh DuraiRead
FirefightingSafety
Sep 30, 2026 · 4 min read

Why Do Car Decks Explode During a Fire?

Most bangs on a burning car deck are tyres, struts and airbag inflators failing. The real blast risk is gas building up in a sealed deck.

By Vignesh DuraiRead
RegulationCompliance
Sep 25, 2026 · 2 min read

What Port State Control Checks on Decks

Fire safety was the leading deficiency area in the Paris MoU's 2025 report, and a 2026 campaign targets cargo securing. What PSC checks on a vehicle deck.

By Vignesh DuraiRead