In brief
MSC.1/Circ.1430 is the design and approval standard for drenchers on vehicle decks. SOLAS II-2/20 requires a fixed water-based system in special category spaces and in spaces that cannot be sealed. The FSS Code says such systems are approved under IMO guidelines, and this circular is that guideline.
It allows two routes: a prescriptive design using minimum water densities and coverage areas that rise with deck height, or a performance-based design proven by fire tests.
Who it applies to
- Fixed water-based fire-fighting systems (drenchers, sprinklers) for open and closed ro-ro spaces and special category spaces.
- Administrations apply Rev.3 when approving systems installed on or after 1 January 2024. FSS Code Chapter 7 (2.4) makes approval under IMO guidelines the route for these systems.
What it requires
- Table 4-1
- Decks up to 2.5 m high
Deluge: 5 mm/min over two adjacent sections of 20 m × full breadth. Wet, dry or pre-action sprinklers: 6.5 mm/min over 280 m².
- Table 4-2
- Decks over 2.5 m and up to 6.5 m
Deluge: 10 mm/min. Wet-pipe sprinklers: 15 mm/min over 280 m²; dry or pre-action: 15 mm/min over 365 m².
- Table 4-3
- Decks over 6.5 m and under 10.0 m
Deluge: 15 mm/min. Wet-pipe sprinklers: 20 mm/min over 280 m²; dry or pre-action: 20 mm/min over 365 m².
- 4.1–4.2
- Design basis
Sprinkler systems cover the hydraulically most demanding area; deluge systems the two adjacent sections with the greatest demand. Minimum operating pressure 0.05 MPa (sprinkler) or 0.12 MPa (deluge).
On a vehicle deck
Water density, written in mm/min (one mm/min equals one litre per minute per square metre), scales with deck height. A figure of 5 L/min/m² is correct only for a deluge system on a deck of 2.5 m or less; taller vehicle decks need 10 or 15.
A deluge system works by sections, and the crew must open the right one. That is why SOLAS now requires ro-pax detection sections and camera views to match the drencher sections: the alarm should tell the crew which valve to open.
On the timeline
Full timeline →- May 2012Drencher design guidelines approved
MSC 90 approves MSC.1/Circ.1430, the design and approval standard for water-based systems in ro-ro and special category spaces.
- 27 Jun 2023Drencher guidelines Rev.3
MSC.1/Circ.1430/Rev.3 issued, applied to systems installed from 1 January 2024.
Discussed in our articles
7 articles cite MSC.1/Circ.1430/Rev.3, newest first.
- Is Shore Power a New Fire Risk at the Berth?Blogs
- Should a Drencher Be Released From the Bridge?Blogs
- Can Crews Find the Right Drencher in Smoke?Blogs
- Does an EV Fire Burn Bigger Than a Petrol Car?Technical Articles
- How Many Cars Does One Deck Detector Watch?Technical Articles
- RoRo Fire Protection: EV Fire DetectionBlogs
- PCTC Drencher Zoning and Fixed-FirstTechnical Articles
Sources we checked
- IMO — MSC.1/Circ.1430/Rev.3, 27 June 2023: history (MSC 90, May 2012; Rev.1 MSC 100, December 2018; Rev.2 MSC 102, November 2020), application to systems installed on or after 1 January 2024, Tables 4-1 to 4-3, paragraphs 4.1–4.2 (read in full). (opens in a new tab)
- IMO — Resolution MSC.339(91): FSS Code Chapter 7 2.4, water-based systems for ro-ro spaces approved under IMO guidelines. (opens in a new tab)
These pages are RoRoSAFE’s plain-English summaries, written for orientation and checked against the sources listed. They are not legal advice and do not replace the official text, which prevails. IMO conventions and codes are published by IMO; we link to official and free copies rather than reproducing them.