Can a Car Carrier Shut Its Vents Once It Burns?

Often not. Fremantle Highway's vents shut only by hand, and their smoke cut off the lifeboats. SOLAS accepts manual closure; remote is optional.
Often not from where it matters. On Fremantle Highway in 2023 the cargo vents were opened for the foam system, and once the fire spread they could only be closed by hand at local butterfly dampers. Smoke from those vents became the crew's main hazard and kept them from the lifeboats. SOLAS accepts manual closure; remote closure is an option.
Closing the space is what makes a fixed gas or foam system work, so this is not a detail. SOLAS allows those systems only in vehicle and ro-ro spaces that can be sealed from outside the cargo spaces. Two recent car-carrier casualties, Fremantle Highway and Grande Costa d'Avorio, lost the same thing: a closing device nobody could reach once the fire held the space.
What does SOLAS require of car-deck vents?
Closure from outside the space, not from the bridge. SOLAS II-2/20.3.1.4.1 says arrangements 'shall be provided to permit a rapid shutdown and effective closure of the ventilation system from outside of the space in case of fire, taking into account the weather and sea conditions'. IMO's unified interpretation in MSC.1/Circ.1434 of 31 May 2012, which IACS applies as UI SC243, says what that means in practice:
- Access routes to the closing controls are clearly marked and at least 600 mm wide.
- Routes across an exposed deck have a handrail or wire lifeline of at least 10 mm, on stanchions no more than 10 m apart.
- Closing devices 1.8 m or more above the deck have ladders or steps.
- Alternatively, remote closing with position indicators on the bridge or at a fire control station is acceptable.
IACS societies apply SC243 to ships contracted for construction from 1 January 2012, and its first revision from 2013. Read together, a car carrier built to this interpretation complies if a crew member can walk a marked route and close each vent by hand. Remote closure is one way to comply, not the required way. The interpretation is written around weather and sea conditions; it says nothing about reaching a damper through smoke.
What happened to Fremantle Highway's vents?
They were opened for the foam, and could not be shut once the fire spread. Panama's flag-state report, made public in January 2026, says the ship had vent fans along each side down to the cargo holds, some of them used as purging vents when foam is released. Before the foam went in, the chief officer told the fire team to check the cargo vents were open. The foam system started at about 23:31, about 21 minutes after the first alarm, and the fire teams reported more smoke, 'most probably coming out of the vent'. The foam ran for about 40 minutes and used about 13 m³ of concentrate without any effect on the fire.
According to the crew, the smoke from the cargo vents was the main hazard on board. It cut visibility and made breathing difficult, and they could not reach the lifeboats or liferafts. Panama considers that closing the vents once the foam was in might have reduced the smoke and given the crew time to use them, but notes that this was almost impossible: the vents had to be closed manually and locally at butterfly dampers, and no remote closure was fitted. Seven crew later jumped about 30 m into the sea, and one died.
Why is a manual damper the weak point?
Because the route to it can run through the fire's smoke and heat. A car carrier's cargo decks run fore and aft with ramps between them, so smoke spreads along and between decks; on Fremantle Highway the chief officer could see it below him looking down the ramps. Panama's recommendation DD says plainly that the vents 'cannot be closed locally due to the heat and flames', and asks for remote emergency closure. A route that meets the 600 mm width and handrail rules can still be impassable.
The NTSB found the same principle at Port Newark. On Grande Costa d'Avorio in July 2023 the crew released CO₂, but could not shut one fire-boundary garage door, because its control panel was inside the fire zone and there were no operating controls outside. The NTSB identified that open boundary as a cause of the CO₂ system's ineffectiveness. Whether the device is a door or a damper, a control the crew cannot reach during the fire does not seal the space.
Do the foam and the vents work against each other?
On Fremantle Highway, yes. Its foam system needed the cargo vents open, and the open vents then let out the smoke that blocked the crew's escape. That makes the vents part of the foam system's design, not only part of the ventilation. Someone has to decide when they open, when they close and how, and on this ship the 'how' depended on reaching the dampers by hand.
A gas system has the opposite need. Before CO₂ is released, the fans are stopped and the openings closed, so the gas stays in the space. Either way the crew has to control the openings during the fire, and the rules only guarantee they can do so from a position that may be unreachable by then.
What should owners and class check?
Whether each closing device can be reached, and seen, during the fire the ship is most likely to have:
- Walk every closure route in a drill that assumes smoke on the cargo decks, wearing breathing apparatus, and time it.
- Check that the bridge can see whether each cargo-deck vent is open or closed. Position indicators come with the remote alternative and are worth having on their own.
- Price remote emergency closure for cargo-deck vents, as Panama's recommendation DD asks, starting with the vents nearest the accommodation and lifeboats.
- On foam-protected ships, write down the sequence for opening purge vents before discharge and closing them afterwards, and who does each step.
- Make every fire-boundary door operable from outside the zone it protects, the lesson of the NTSB's Grande Costa d'Avorio findings.
- Test dampers closed rather than assuming them closed, as our post on stopping car-deck fans sets out.
How RoRoSAFE helps
A vent nobody can reach stays open. Both Fremantle Highway and Grande Costa d'Avorio lost closing devices once the fire held the space. RoRoSAFE acts earlier: infrared thermal and battery-vent gas sensing beneath each parked vehicle, with tiered bridge and shore alerts naming the deck and bay before visible smoke, so closing decisions start while routes are still clear. It complements SOLAS systems and holds no class type approval yet.
Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access
Sources
- 1. Panama Maritime Authority — Safety investigation report R-016-2024-DIAM, fire on board Fremantle Highway (25 July 2023), made public as an attachment to Dutch parliamentary paper 31409 no. 495 on 27 January 2026: vent fans and purging vents; vents checked open before foam; foam started about 23:31 and ran about 40 minutes, tank from 14 m³ to 1 m³; smoke from cargo vents as the main hazard; manual local butterfly dampers with no remote closure; recommendation DD.5 on remote emergency closure.
- 2. IACS — Unified Interpretation SC243, 'Access to controls for closing of ventilation of vehicle, special category and ro-ro spaces (SOLAS II-2/20.3.1.4.1)', Rev.1, May 2012: regulation text; 600 mm marked routes, handrails or lifelines, ladders for closures 1.8 m and above; remote closing with position indicators as an alternative; application from ships contracted on or after 1 January 2012 (Rev.1 from 2013).
- 3. IMO — MSC.1/Circ.1434, 'Unified interpretations of SOLAS chapter II-2', 31 May 2012, approved at MSC 90: the same interpretation of regulation II-2/20.3.1.4.1.
- 4. IMO — MSC 110/18/12 (Bahamas, Cook Islands, Türkiye and IACS), 18 March 2025: quotes SOLAS II-2/20.6.1.1, under which fixed gas and high-expansion foam systems are permitted in vehicle and ro-ro spaces 'capable of being sealed from a location outside of the cargo spaces'.
- 5. NTSB — Marine Investigation Report MIR-25/16, fire aboard Grande Costa d'Avorio, Port Newark, 5 July 2023 (board meeting 15 April 2025): fire-boundary door control inside the fire zone with no outside controls, identified as a cause of the CO₂ system's ineffectiveness. As covered in RoRoSAFE's case study.
- 6. Dutch Safety Board — 'Emergency assistance Fremantle Highway', May 2025: seven crew jumped about 30 m and one died. As covered in RoRoSAFE's case study 'Fremantle Highway — Anatomy of a Late Rescue'.
Questions, answered
Does SOLAS require remote closure of car-deck vents?+
No. SOLAS II-2/20.3.1.4.1 requires rapid shutdown and effective closure of the ventilation from outside the space. IMO's interpretation, MSC.1/Circ.1434, accepts clearly marked manual routes at least 600 mm wide, with handrails and ladders where needed. Remote closing with position indicators on the bridge or at a fire control station is an accepted alternative, not a requirement.
What went wrong with Fremantle Highway's vents?+
They were opened for the fixed foam system, which then ran for about 40 minutes without effect. Smoke from the open cargo vents became the crew's main hazard and kept them from the lifeboats. Panama's flag-state report says closing them was almost impossible, because they had to be shut by hand at local butterfly dampers and no remote closure was fitted.
Why are cargo vents opened when foam is released?+
On Fremantle Highway some cargo-deck vents served as purging vents for the foam system, so the crew checked they were open before discharge. Panama's report suggests closing them once the foam is in, to cut the smoke reaching the decks the crew needs. That only works if the vents can be closed remotely, since local dampers may be unreachable in heat and smoke.
What should a car-carrier owner check about vent closure?+
Whether every closing device can be reached with breathing apparatus during a smoke-filled drill, whether the bridge can see each vent's position, and what remote emergency closure would cost. Foam-protected ships also need a written sequence for opening and closing purge vents, and every fire-boundary door should be operable from outside the zone it protects.
Continue the thread

Should Car-Deck Fans Stop in an EV Fire?
Yes — stopping the fans starves the fire and lets CO₂ work. But a sealed deck also traps battery vent gas, so when and how you reopen it matters as much.

Grande Costa d'Avorio: Fatal Loading Fire
The NTSB traced the fatal 2023 Grande Costa d'Avorio fire to a Jeep used as a cargo pusher — and a CO2 system the crew could not seal off.
Fremantle Highway — Anatomy of a Late Rescue
The Dutch Safety Board faulted the Fremantle Highway rescue; Panama's flag-state report traced the fire to an EV. Seven crew jumped ~30 m and one died.

What Did Fremantle Highway's Fire Alarms Show?
Where, not what. Four smoke alarms in a minute put the fire beside 24 BMW EVs on deck 8, but the crew suspected a fault. Foam came 21 min later.

When Should a Car-Carrier Crew Abandon Ship?
When the fixed system stops holding. Min Jiang Kou put 22 crew in lifeboats in August 2026; AMVER ships had them aboard within 23 hours.

Should IMO Write a Code for EV Carriers?
Panama says yes after Fremantle Highway, but most of what it asks for is a car-carrier design code, and IMO's route runs through 2027 guidelines.