How Should You Run a Fire-Detection Pilot?

By Vignesh Durai · · 5 min read

As an experiment with a decision at the end: one deck, every operating mode, pass/fail numbers set before install, and a third party to sign it.

As an experiment with a decision at the end. Fit one deck, run it long enough to see every operating mode, write the pass/fail numbers before installation, and have someone outside the vendor sign the result. Most detection pilots fail as experiments. They run without criteria, they produce a slide deck, and the fleet decision quietly never gets made.

Choosing a system and proving it on your ship are different jobs. Our guide to evaluating PCTC fire detection covers the first. This post covers the second: how long a deck pilot should run, what you can and cannot test, which numbers decide it, who signs, and how to make sure the pilot ends in a scale-or-stop decision rather than an extension.

935
Alarms a weather-deck camera logged in 4 loading days, EMSA FIRESAFE II
1 in 4
Ro-ro fires that start in port or just after departure, FIRESAFE II
11 / 7
Silences and resets before Commodore Clipper's detection failed, MAIB 24/2011
3
FSS Code conditions for linking another system to fire detection

How long should a deck pilot run?

Long enough to see every way the deck is used, not just a calm passage. The failure modes that kill detection credibility are concentrated in specific conditions. In FIRESAFE II, a weather-deck thermal camera on Stena Scandinavica logged 935 alarms in four days, all during cargo operations. The same study found that basically all ro-ro ships switch smoke detection off while loading, and that about one in four ro-ro fires starts in port or just after departure.

So a pilot has to cover many full loading and discharge cycles, a full cargo mix including EVs, hybrids and used vehicles, ventilation changes, hot and cold weather, and at least one port stay. In practice that means months, not weeks. Allow for a calibration period at the start, state its length in advance, and exclude it from the scored window, so the system is judged on settled behaviour rather than its first week.

What can you actually test on a working deck?

Faults and surrogates you can stage, and everything else by observation. Nobody will set a car on fire on a loaded deck, so the pilot cannot prove fire detection directly at sea. Split it deliberately:

  • Staged, scheduled and logged: safe heat sources at chosen vehicles, certified test gas at gas sensors, and deliberate faults such as a disconnected sensor or a power interruption, to prove the system reports its own failures.
  • Observed: every alarm and fault over the scored window, with time, deck, bay, operating mode and cause, recorded alongside what the SOLAS detectors and crew patrols did at the same time.
  • Borrowed: detection performance against real lithium-ion runaway comes from bench and laboratory test data, which the pilot should cross-reference rather than try to repeat.

If the pilot system connects to the ship's fire alarm panel, add one more staged test. FSS Code Chapter 9 paragraph 2.1.3 allows the link only if the other system can be disconnected without losing any required function, and its malfunction cannot propagate to the fire detection system. Disconnect it during the pilot and show that nothing required changed.

Which numbers should decide pass or fail?

Numbers chosen by the owner before installation, not after. Criteria written once the data is in tend to fit the data. The targets below are illustrative and should be set for your ship and fleet, but each one should be a number, not a judgement.

  • Staged-event detection: every staged heat and gas event detected, at the correct deck and bay, within an agreed time.
  • Nuisance rate by operating mode: alarms per day at sea and per loading operation, each with a recorded cause, with a ceiling for alarms that reach the bridge.
  • Alarm flooding: no more alarms in ten minutes than a watch can handle. The process-industry benchmark EEMUA 191 treats more than ten in ten minutes as a flood.
  • Fault reporting: every staged fault reported as a fault, not missed and not reported as fire.
  • Availability: the share of the scored window the system was fully monitoring, with every gap explained.
  • Crew response: time from alarm to acknowledgement and to someone at the bay, and the crew's own rating of whether they trusted it by the end.
Crew trust is a pass/fail criterion, not a soft extra. On Commodore Clipper in 2010 a real fire read as a detector fault: the alarm was silenced 11 times and reset 7 times before the system failed, and confirming the fire took 17 minutes. A system the crew learns to ignore is worse than no system.

Who should sign the result?

Everyone whose decision depends on it, agreed at the start. That means the owner's technical superintendent, the master and the officers who stood watch with the system, and ideally class and the hull or P&I underwriter. They should agree the criteria up front and receive the same evidence at the end, not a vendor summary. Settle three practical points before installation:

  • Evidence format: raw alarm and fault logs, tamper-evident and exportable, so a third party can recount every number in the report.
  • Data ownership: who owns the pilot data, and whether the owner can share it with insurers, class and charterers.
  • Reporting rhythm: a monthly summary against the criteria, so a failing pilot is visible early rather than at the end.

How do you stop a pilot from stalling?

Put the decision in the plan. Fix the decision date and decision owner before the pilot starts. Define what a pass, a fail and a conditional extension each mean, with one extension at most and its own criteria. Know in advance what scaling would require: other decks, sister ships, budget and installation windows.

Then tie the decision to dates that already matter. Existing ro-pax ships must add heat detection in vehicle spaces by their first survey after 1 January 2028. P&I and hull renewals reward evidence that is ready before submissions close. A pilot timed to finish ahead of those dates produces a result someone has to act on.

Conclusion

How RoRoSAFE helps

A RoRoSAFE pilot is built to run this way: one deck, installed alongside the berth in about three working days with no drydock and no drilling, then six months of bridge and shore dashboard access. Per-vehicle thermal and battery-vent gas alerts name the deck and bay, and tamper-evident, export-ready logs let a third party check every number. It ends in a joint insurer and class review. RoRoSAFE holds no class type approval and complements SOLAS detection.

Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access

Sources

  • 1. EMSA — FIRESAFE II, Work Package 4 final report (Bureau Veritas, RISE, Stena Rederi), December 2018: weather-deck thermal camera on Stena Scandinavica logged 935 alarms 26–30 August, all during cargo operations; smoke detection deactivated during loading on basically all ships; about one in four ro-ro fires in port or just after departure (as summarised in RoRoSAFE's posts on FIRESAFE II and on detection during loading).
  • 2. UK MAIB — Report 24/2011, fire on Commodore Clipper (2010): alarm silenced 11 times and reset 7 times before the system failed; 17 minutes from first alarm to confirmed fire, as summarised in RoRoSAFE's 'What a False Alarm Costs a Master at Sea'.
  • 3. IMO — Resolution MSC.311(88), FSS Code Chapter 9 para 2.1.3: conditions for connecting a decision management system to the fire detection system.
  • 4. EEMUA Publication 191, Alarm Systems: steady-state and flood alarm-rate benchmarks, as summarised in RoRoSAFE's 'How Many Alarms Can a Bridge Team Absorb?'.
  • 5. IMO — Resolution MSC.550(108), SOLAS II-2/20 amendments for ro-ro passenger ships: existing ships to comply by the first survey on or after 1 January 2028 (Lloyd's Register Class News 07/2026).
  • 6. RoRoSAFE pilot terms — one deck, installed alongside the berth in about three working days, six months of dashboard access, joint insurer and class review (RoRoSAFE FAQ).
Frequently asked

Questions, answered

How long should a ship fire-detection pilot last?+

Long enough to cover every operating mode: many loading and discharge cycles, a full cargo mix, ventilation changes, seasonal weather and port stays. In practice that is months rather than weeks. Nuisance alarms concentrate during cargo operations, and about one in four ro-ro fires starts in port or just after departure, so a calm-passage trial proves little.

Can you test fire detection on a working car deck?+

Partly. Nobody stages a vehicle fire on a loaded deck, so a pilot stages safe surrogates instead: heat sources, certified test gas and deliberate faults. It observes every real alarm against the ship's SOLAS detectors and patrols. Detection of real battery thermal runaway is proven in the laboratory and cross-referenced, not repeated at sea.

What criteria should a detection pilot be judged on?+

Numbers fixed before installation: staged events detected at the right deck and bay, nuisance alarms per operating mode with causes, an alarm-flood ceiling, fault reporting, system availability, crew response times and the crew's own trust rating. Criteria agreed after the data arrives tend to fit the data, so write them first.

Who should review the results of a ship detection pilot?+

The owner's technical superintendent, the officers who stood watch with it, and ideally class and the underwriter. They should agree the criteria at the start and receive the same raw, tamper-evident logs at the end rather than a vendor summary, so any of them can recount the numbers.

Related reading

Continue the thread

DetectionPCTC
Sep 25, 2026 · 6 min read

How to Evaluate Fire Detection for a PCTC

Judge PCTC fire detection on five things: how early it alarms, proven coverage on a loaded deck, false-alarm data, approvals and installation downtime.

By Vignesh DuraiRead
RegulationDetection
Oct 16, 2026 · 4 min read

Does Extra Fire Detection Need Class Approval?

Not as a SOLAS system if it replaces nothing. But it must never degrade required detection, and its wiring and interfaces still need class sign-off.

By Vignesh DuraiRead
DetectionSafety
Aug 13, 2026 · 5 min read

How Many Alarms Can a Bridge Team Absorb?

EEMUA 191 caps steady state at one alarm per ten minutes. Marine sets no equivalent rate target, and 2026 multiplies the addressable points.

By Vignesh DuraiRead
OperationsDetection
Sep 22, 2026 · 7 min read

What a False Alarm Costs a Master at Sea

Seventeen minutes, in the one case with timestamps. On Commodore Clipper a real fire read as a detector fault: 11 silences, 7 resets, then the system died.

By Vignesh DuraiRead
RegulationSafety
Sep 19, 2026 · 6 min read

Is Fire Detection Off While the Ship Loads?

Usually, yes — smoke sections are muted while loading. From 2026 the FSS Code allows it but keeps heat detection on; 1 in 4 ro-ro fires start in port.

By Vignesh DuraiRead
Reference scenarioInsurance
Jul 6, 2026 · 3 min read

Scenario: How Insurers Evaluate Detection

Reference scenario: how a hull underwriter, a Lloyd's syndicate, a P&I club and a loss adjuster would test whether detection evidence holds up.

By Vignesh DuraiRead
InsuranceP&I
Oct 16, 2026 · 4 min read

What Will the 2027 P&I Renewal Ask of RoRo?

Brokers expect a 2.5–5% general increase at the February 2027 P&I renewal. For car carriers and ro-ros, each fleet's own fire record sets the real price.

By Vignesh DuraiRead