How Many Cars Does One Deck Detector Watch?

By Vignesh Durai · · 5 min read

About 7 to 9 cars per smoke detector and 4 per heat detector under the 2026 FSS spacing, with the worst-placed car about 6 m from the nearest head.

About seven to nine parked cars per smoke or combined detector, and about four per heat-only detector. That follows from the FSS Code's 2026 spacing rules and typical car-carrier stowage gaps. On a compliant grid, the car farthest from any detector sits about 6 m away horizontally. The numbers explain why a ceiling alarm tells the bridge roughly where a fire is, but not which vehicle.

74 m²
Maximum floor area per smoke or combined smoke-and-heat detector, FSS Code Table 9.1
7–9
Cars under one 74 m² detector at standard stowage gaps (calculated)
~6 m
Worst-case horizontal distance from a car to the nearest combined detector (calculated)
37 m²
Maximum floor area per heat-only detector, about 4 cars

What spacing does the FSS Code allow?

Area and distance limits that depend on the detector type, set in chapter 9 of the FSS Code and updated by resolution MSC.555(108) from 1 January 2026. Table 9.1 sets these limits:

  • Heat detectors: at most 37 m² of floor area each, no more than 9 m apart, and within 4.5 m of a bulkhead.
  • Smoke detectors: 74 m² each, 11 m apart, and within 5.5 m of a bulkhead.
  • Combined smoke-and-heat detectors: 74 m² each, but 9 m apart and within 4.5 m of a bulkhead.
  • Linear heat cables: no more than 9.0 m apart and within 4.5 m of a bulkhead.

Heat detectors must operate between 54 °C and 78 °C when the temperature rises at less than 1 °C per minute. On new ro-pax ships, smoke detection may be disconnected during loading and unloading, with an automatic reset, but heat detection and manual call points may not be.

Both the area and the distance limit apply at once. For a square grid of combined detectors, the area limit binds first: √74 gives a grid about 8.6 m on a side, inside the 9 m distance limit. For heat-only detectors, √37 gives a grid about 6.1 m on a side.

How many cars sit under one detector?

Seven to nine, depending on the car. Wallenius Wilhelmsen's published stowage standard leaves 10 cm side to side, measured to body or mirror, and 30 cm bumper to bumper between cars. Each car therefore occupies its own footprint plus 0.1 m of width and 0.3 m of length.

  • A compact hatchback such as the Volkswagen Golf 8 (4.284 m × 1.789 m) needs a cell of about 4.58 m × 1.89 m, or 8.7 m². That gives about 8.5 cars per 74 m² detector and 4.3 per 37 m² heat detector.
  • A mid-size electric SUV such as the Tesla Model Y (4.790 m × 1.920 m without mirrors, per its owner's manual) needs about 5.09 m × 2.02 m, or 10.3 m². That gives about 7.2 cars per 74 m² detector and 3.6 per heat detector. With mirrors unfolded (2.129 m wide), the cell grows to about 11.3 m², or 6.5 cars per detector.

Walkways, which the same standard sets at 60 cm, together with ramps, pillars and lashing lanes, lower the real density a little. On a full car deck, each smoke or combined detector still watches a block of roughly seven to nine vehicles. Each heat-only detector watches about four.

How far can a burning car be from the nearest detector?

About 6 m horizontally in the worst case, more next to a bulkhead. In a square grid, the point farthest from any detector is the centre of the square, half a diagonal from each corner. For combined detectors at 8.6 m, that is about 6.1 m. For heat-only detectors at 6.1 m, it is about 4.3 m. Smoke detectors placed in a rectangular pattern at the full 11 m spacing reach about 6.4 m. A car stowed against a bulkhead can be up to 4.5 m or 5.5 m from the line of detectors, on top of its position along the line.

Distance matters because the gases from a fire reach the deckhead and spread outward, thinning and cooling as they go. Alpert's ceiling-jet correlation, the one used in this site's article on heat-detector response, makes the effect concrete. Take an illustrative 50 kW early-stage fire under a 2.5 m deckhead. Directly above it, the gas is about 50 °C warmer than ambient, enough to reach a 54–78 °C heat detector. At 4.3 m away the rise is about 11 °C, and at 6.1 m about 9 °C, well short of it. The same fire, positioned differently relative to the grid, can be seen within seconds or missed until it grows several times larger.

Smoke travels further before it thins, but it has its own obstacles. ClassNK's EV transport guidelines point out that deck beams and girders can delay smoke reaching a detector, and that tightly loaded vehicles make the source hard to pin down. Ventilation, which must keep running on a working deck, dilutes smoke before it arrives.

What does an alarm actually tell the bridge?

A neighbourhood, not a car. On an older zone system, the alarm names a section. Drencher sections under MSC.1/Circ.1430/Rev.3 are designed in lengths of 20 m across the full breadth of the deck. On a deck 30 m wide, that is 600 m², or roughly 58 to 69 cars at the stowage densities above.

From 2026, new ro-pax ships must have individually identifiable detection, so the alarm names a single detector. That narrows the search to the block under one 74 m² head, roughly seven to nine cars, if the fire is close to it. If the fire sits between heads, it may trip several detectors at once or reach none of them early.

Either way, someone still has to find the vehicle. ClassNK's guidelines say plainly that in tightly loaded spaces it may take a considerable time to identify which vehicle is on fire using smoke detectors alone. On a car deck, that search is the step that separates a fire caught at one vehicle from a fire that has reached its neighbours.

What would tighter coverage take?

More heads, or a different layer. Halving the spacing of a grid quadruples the number of detectors, from one per seven to nine cars to about one per two. That is a large cabling and maintenance burden for a modest gain, because each head still waits for heat or smoke to reach the deckhead. Linear heat cable gives a continuous reading along its length, but the cables are still up to 9 m apart and still overhead. Aspirating systems sample air more sensitively, but SOLAS does not allow them in open ro-ro or special category spaces. Cameras cover a wide area but lose line of sight between closely stowed vehicles.

The alternative is to measure at the vehicle, where the first signs of a battery failure appear: heat from the pack under the car and electrolyte vapour before smoke. A sensor per vehicle changes the question the alarm answers, from which part of the deck to which car. That layer sits above the SOLAS grid rather than replacing it. The regulated detectors still have to meet Table 9.1.

Conclusion

How RoRoSAFE helps

A compliant deckhead grid gives one detector per seven to nine cars and can leave the worst-placed car 6 m from the nearest head. RoRoSAFE puts infrared thermal and battery-vent gas sensing under each parked vehicle, so tiered bridge and shore alerts name the deck and bay before visible smoke, not just a section. It installs alongside the berth, with no drydock and no vehicle modification. It complements SOLAS detection and suppression; it replaces neither.

Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access

Sources

  • 1. IMO, Resolution MSC.555(108), amendments to the FSS Code (in force 1 January 2026), as summarised in this site's regulations library. FSS Code chapter 9, Table 9.1: heat 37 m², 9 m, 4.5 m; smoke 74 m², 11 m, 5.5 m; combined 74 m², 9 m, 4.5 m; linear heat no more than 9.0 m apart and 4.5 m from bulkheads. §2.3.1.3: heat detectors operating between 54 °C and 78 °C. §2.5.1.4: disconnection of smoke detection during loading on new ro-pax ships, but not heat detection or call points.
  • 2. IMO, SOLAS II-2/20.4.1 as amended by MSC.550(108): individually identifiable smoke and heat detection on new passenger ships. MSC.1/Circ.1430/Rev.3: deluge sections designed as 20 m × full breadth.
  • 3. Wallenius Wilhelmsen, Cargo Handling Instruction, 'Stowage distances': cars 10 cm side to side (body or mirror), 30 cm bumper to bumper, 60 cm walkway; manufacturer requirements take priority.
  • 4. Vehicle dimensions: Tesla, Model Y Owner's Manual (UK), dimensions: overall length 4,790 mm, width 1,920 mm excluding mirrors and 2,129 mm including mirrors (varies with options). Volkswagen Golf 8 launch specifications (October 2019, via Paul Tan and CarExpert): 4,284 mm × 1,789 mm.
  • 5. Alpert, R.L., 'Calculation of response time of ceiling-mounted fire detectors', Fire Technology 8 (1972): ceiling-jet correlations ΔT = 16.9 Q^(2/3)/H^(5/3) for r/H ≤ 0.18 and ΔT = 5.38 (Q/r)^(2/3)/H beyond. The 50 kW and 2.5 m inputs are illustrative, not measured values.
  • 6. ClassNK, 'Guidelines for the Safe Transportation of Electric Vehicles', Edition 2.0 (December 2024), §5.2.2: smoke delayed by beams and girders, and the time needed to identify the burning vehicle with smoke detectors alone in tightly loaded spaces.
Frequently asked

Questions, answered

How far apart are fire detectors on a ro-ro vehicle deck?+

Under FSS Code Table 9.1, as amended from 2026, heat detectors cover up to 37 m² each and sit no more than 9 m apart. Smoke detectors cover 74 m² and may be 11 m apart. Combined smoke-and-heat detectors cover 74 m² at 9 m spacing. Each type must also be within 4.5 m, or 5.5 m for smoke, of a bulkhead.

How many cars does one smoke detector cover on a car deck?+

Roughly seven to nine. Allowing 10 cm between cars side to side and 30 cm bumper to bumper, a compact car occupies about 8.7 m² and a mid-size electric SUV about 10.3 m². A 74 m² detector area therefore spans about 8.5 compact cars or 7 SUVs. A heat-only detector, at 37 m², covers about four.

Does an individually identifiable detector show which car is on fire?+

No. It shows which detector alarmed, which narrows the search to the block of about seven to nine cars under it, if the fire is close to that head. A fire between heads can trip several or none early. ClassNK notes that identifying the burning vehicle with smoke detectors alone can take considerable time in tightly loaded spaces.

Why does distance from the detector matter so much?+

Fire gases cool and thin as they spread along the deckhead. Using Alpert's ceiling-jet correlation, an illustrative 50 kW fire under a 2.5 m deck raises the gas about 50 °C directly above it but only about 9 °C at 6 m away. A heat detector set at 54–78 °C may respond quickly to one and not at all to the other.

Related reading

Continue the thread

DetectionSOLAS
Oct 19, 2026 · 6 min read

When Does a Heat Detector Alarm on a Car Deck?

Once the fire is real. Ceiling gas must reach 54 °C: about 330 kW of fire on a 2.5 m deck, 1.6 MW on a 6.5 m one. A venting battery gives neither.

By Vignesh DuraiRead
RegulationDetection
Sep 15, 2026 · 7 min read

Is Individually Identifiable Detection Required?

On a passenger ship, since 2012 — the FSS Code defines the term. On a car carrier, no: MSC.550(108) leaves cargo ships at section identification.

By Vignesh DuraiRead
SensingDetection
Oct 17, 2026 · 5 min read

Does a Battery Vent Plume Reach the Ceiling?

Often not at first. Early electrolyte vapour is 2–3× denser than air and stays low; only the hot runaway gas rises fast enough for ceiling detectors.

By Vignesh DuraiRead
SensingSOLAS
Jul 21, 2026 · 5 min read

Does Deck Ventilation Delay Fire Detection?

Yes. SOLAS II-2/20 mandates continuous ventilation on closed vehicle decks, and that airflow dilutes smoke and off-gas before detectors see it.

By Vignesh DuraiRead
SensingFiber-Optic
Aug 27, 2026 · Updated Oct 24, 2026 · 5 min read

Fiber-Optic Linear Heat Detection on RoRo

SOLAS has required heat detection on new ro-pax vehicle decks since 1 January 2026 — and a line-type detector answers that with a cable, not a grid.

By Vignesh DuraiRead
SensingDetection
Jun 25, 2026 · Updated Oct 24, 2026 · 4 min read

Aspirating vs Point Smoke on Vehicle Decks

Point detectors alarm only once diluted smoke reaches the deckhead; aspirating (ASD) systems sample air continuously and trip far earlier.