Resolution

MSC.555(108)

Resolution MSC.555(108) — Amendments to the International Code for Fire Safety Systems (FSS Code)

In forceIMO Maritime Safety Committee, 108th sessionChecked 18 October 2026

MSC.555(108) amends FSS Code chapters 7 and 9 from 1 January 2026: weather-deck monitors, heat-detector specs and spacing, and ro-pax alarm rules.

In brief

MSC.555(108) is the engineering half of the 2026 package. Where MSC.550(108) says what a vehicle deck must have, MSC.555(108) specifies how the weather-deck monitors and the detectors must perform.

It was adopted on 23 May 2024 alongside MSC.550(108) and entered into force on the same date, 1 January 2026.

Who it applies to

  • Chapter 9 generally applies to ships constructed on or after 1 July 2012; the new linear-heat test standard (2.3.1.5) and spacing table (2.4.2.2) apply to ships constructed on or after 1 January 2026.
  • The new weather-deck monitor specification (Chapter 7, 2.5) and the alarm-presentation and loading-disconnection rules (Chapter 9, 2.5.1.2–2.5.1.4) apply to ro-ro passenger ships constructed on or after 1 January 2026.

What it requires

FSS 7, 2.5
Weather-deck monitors (new ro-pax)

Monitors covering the full weather-deck vehicle area and superstructure boundaries within 8.0 m; at least 2.0 L/min per m² combined and no monitor below 1,250 L/min; farthest point within 75% of throw in still air; water supply for the full width over 40 m of length.

FSS 9, 2.3.1.3
Heat detector response

Heat and linear heat detectors certified to operate before 78 °C but not below 54 °C at rises of less than 1 °C/min, tested to EN 54:2001 and IEC 60092-504 or alternatives accepted by the Administration.

FSS 9, 2.3.1.5
Linear heat detection

Linear heat detectors tested to EN 54-22:2015 and IEC 60092-504 (ships built from 2026).

FSS 9, Table 9.1
Detector spacing

Heat: 37 m² per detector, 9 m apart, 4.5 m from bulkheads. Smoke: 74 m², 11 m, 5.5 m. Combined smoke and heat: 74 m², 9 m, 4.5 m. Linear heat cables no more than 9.0 m apart and 4.5 m from bulkheads.

FSS 9, 2.5.1.2–.3
Alarm presentation (new ro-pax)

A consistent alarm scheme on the bridge, alarm addressability, alarm history and suppression that keeps active alarms visible.

FSS 9, 2.5.1.4
Disconnection during loading (new ro-pax)

Smoke detection in special category and ro-ro spaces may be disconnected for loading and unloading, with automatic reset and a visible indication; heat detection and manual call points may not be disconnected.

On a vehicle deck

The loading rule is the clearest sign of how the 2026 package treats vehicle decks: smoke detection is accepted as unreliable while engines run and may be switched off for the operation, while heat detection must stay live. On new ro-pax ships, heat is the detection that is always on.

The spacing table sets the minimum density for ceiling detectors. A ceiling detector at those spacings still waits for heat or smoke to reach the deckhead, which is why some owners add detection close to each vehicle on top of it.

Discussed in our articles

19 articles cite MSC.555(108), newest first.

Show all 19 articles

Sources we checked

  1. IMO — Resolution MSC.555(108), adopted 23 May 2024, in force 1 January 2026: FSS Code Chapter 7 new 2.5; Chapter 9 1.1, 2.3.1.3–2.3.1.5, 2.4.2.2 and Table 9.1, 2.5.1.2–2.5.1.4 (read in full). (opens in a new tab)

These pages are RoRoSAFE’s plain-English summaries, written for orientation and checked against the sources listed. They are not legal advice and do not replace the official text, which prevails. IMO conventions and codes are published by IMO; we link to official and free copies rather than reproducing them.