Should a Drencher Be Released From the Bridge?
Yes on most ferries: EMSA's study costed remote release at about €100,000 and found it pays off. But Lisco Gloria's gave no water, so keep the runner.
Yes, as an addition to the valve room and not a replacement for it. IMO's design guidelines have called for release controls in a manned control station since 2012, but older drenchers may stay in service without them. EMSA's FIRESAFE II study found remote release cost-effective on most ferries. Lisco Gloria shows the limit: a bridge release that produced no water.
Why does releasing a drencher take so long?
Because the decision and the valve are in different places. DNV GL notes that release is started from a deluge control station, often a long way from the wheelhouse, engine control room and crew accommodation. So an alarm on the bridge has to become a confirmed fire, then a section number, then a message to someone who has to reach that station and open the right valve.
The EU's LASH FIRE project mapped this sequence and found bottlenecks: crews looking up which section matches the fire's location, checking whether dangerous goods limit the use of water, and working out who makes the final decision. It says extinguishing can sometimes take 20 minutes or more to start.
DNV GL's 2016 review shows the spread on real ships, measured from ignition to deluge release. Victoria Seaways took 3 minutes and damage stayed limited. Commodore Clipper took 25 minutes. Pearl of Scandinavia took 35, after the wrong section was opened at 17. Engine-room water mist, with several remote release controls, had recorded response times of 0.5 to 2 minutes. DNV GL's view was that lessons from the engine room could shorten the time for ro-ro spaces too.
What do the rules require?
Less than the guidelines suggest, and less again for older ships. As DNV GL put it in 2018, SOLAS only requires manual release of section valves, though remote release speeds activation. The detail sits in IMO's design guidelines for water-based systems, which governments are invited to apply when approving new installations.
- MSC.1/Circ.1430 of 2012 said all release controls for deluge systems should be available and grouped together in a continuously manned control station or the safety centre.
- Rev.3, for systems installed on or after 1 January 2024, asks for release stations in the valve room and in that manned station or safety centre, with controls to start and stop pumps and to open and close section valves.
- The same paragraph asks for remote indication of pump running, valve manifold pressure and whether each valve is open or closed.
- Valves must still be operable by hand, either at the valve or through a control system routed outside the protected spaces, and protected against unauthorised use.
- Systems approved under older standards and installed before 2024 may stay in service as long as they are serviceable.
So the live question is the existing fleet. A ferry with an older manual system can keep sending someone to the valve for as long as that system stays serviceable.
Is it worth fitting on an existing ferry?
On most ferries, yes. FIRESAFE II assessed remote control from the bridge, engine control room or safety centre on three generic ship types, against a limit of €7M per fatality averted. A factor below 1 passes.
- Standard ro-pax: 0.28 on a new ship and 0.61 on an existing one, at about €101,000 and €114,000 over the ship's life. Confidence that the existing-ship figure really is below 1 was 74%.
- Passenger-focused ferry: 0.15 new and 0.33 existing.
- Cargo-focused ro-pax: 2.32 new and 5.13 existing, so it fails, because few passengers means few lives at risk and much of the cargo sits on a weather deck the drencher does not cover.
- Adding CCTV so the officer can confirm the fire before pressing the button gives 0.30 new and 0.65 existing on the standard ro-pax.
Keep the benefit in proportion. The first FIRESAFE study estimated remote control would cut the chance of suppression failure by about 8 to 11%. Better activation routines cut it by about 16%, for an estimated €200. On a ship without remote release, the training comes first, and the hardware follows.
What can go wrong with a bridge button?
It can tell the bridge something happened when it did not. On Lisco Gloria in 2010 the master started the drencher from the bridge within minutes. The section valves opened, but the pump control was most probably set to manual, so no water came, and the bridge never learned why. Remote release had worked exactly as built, and the ship was still lost.
FIRESAFE's authors saw this coming. They listed 'false security' as a risk, noted that a pump left in local mode is still possible, and assumed in their results that a runner still goes to the drencher station on an alarm, or that CCTV confirms the valves. Remote control also adds complexity, which raises the risk of technical failure. Power is a weak point as well: on Sorrento in 2015 the drencher became unusable when main power dropped, probably after fire damaged cables on the deckhead.
Going further to automatic release has its own problems. IMO's guidelines allow it, with flame and smoke detection, colour CCTV across the space and release when two detectors activate, and it may be disconnected during loading. The FIRESAFE project group raised two concerns: large quantities of water released automatically could cause stability problems, and water could hit cargo on a false alarm.
What should an owner do?
Find out what the ship has, then close the gaps in order of cost.
- Check which standard the drencher was approved to, and whether release, pump start and valve position are all available in a manned station.
- If remote release exists, make sure the bridge can see pump running, manifold pressure and valve position. A release without that feedback repeats Lisco Gloria.
- Test release from every station. DFDS's fleet review after Lisco Gloria called for every section valve to be tested from both remote and main control stations.
- Keep the runner in the procedure, with the valve-room task on the muster list.
- Settle who may release. DNV GL's Anders Tosseviken advises delegating water-based systems to the lowest possible level and defining release times; DNV GL's own example target is 3 minutes. FIRESAFE II also backed giving crews the mandate to activate early without fear of consequences, at a factor of 0.35 on an existing standard ro-pax.
- If the ship has no remote release, price it together with CCTV at the next docking.
None of this transfers directly to CO₂ on a car carrier. The Vehicle Carrier Safety Forum's drill guidelines reflect a full muster and headcount before gas goes in, while a deluge or water-mist release may be ordered before muster is complete. DNV GL adds that a deluge, unlike CO₂, does not need the ventilation shut down first.
How RoRoSAFE helps
A bridge button only saves time if the officer already knows which section to press. Much of the delay is in finding and confirming the fire. RoRoSAFE puts infrared thermal and battery-vent gas sensing under each parked vehicle and sends bridge and shore alerts naming the deck and bay before visible smoke. It does not confirm that water is flowing, and it complements SOLAS detection and the drencher rather than replacing either.
Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access
Sources
- 1. IMO — MSC.1/Circ.1430/Rev.3, 27 June 2023 (copy published by the Hong Kong Marine Department): application to systems installed on or after 1 January 2024; existing systems; paragraphs 3.1, 3.2, 3.2.1, 3.2.2 and 5.6 (read in full).
- 2. IMO — MSC.1/Circ.1430, May 2012 (Dutch government copy, NeRF): paragraph 3.23 on release controls in a continuously manned control station or safety centre.
- 3. DNV GL — 'Fires on Ro-Ro Decks', paper no. 2016-P012, April 2016: deluge control station location, release times, engine-room water mist response, release-time goals (read in full).
- 4. DNV GL — 'Effective mitigation of fire risks on board', 5 March 2018: SOLAS manual release of section valves, remote release, Anders Tosseviken's advice on delegation and release times.
- 5. EMSA — FIRESAFE II, Combined Assessment Final Report, version 1.1, December 2018, by Bureau Veritas, RISE and Stena: remote control, CCTV and early-activation options; Tables 12, 13, 16 and 17; €7M criterion; section 11 (relevant sections read).
- 6. EMSA — FIRESAFE study, EMSA/OP/01/2016, by SP, Bureau Veritas and Stena Rederi: remote control and automatic release options (sections 4.2.1 and 4.2.12), runner assumption, Table 4.4-1, costs (relevant sections read).
- 7. LASH FIRE — Work Package 7 project page: bottlenecks in activating fixed extinguishing systems; time from detection to extinguishing.
- 8. BSU (Lisco Gloria), DIGIFEMA (Sorrento) and the Vehicle Carrier Safety Forum's Fire Drill Guidelines. Covered with their sources in the linked Lisco Gloria and Sorrento case studies and the linked post on car-carrier fire drills.
Questions, answered
Does SOLAS require a drencher to be released from the bridge?+
SOLAS itself only requires manual release of section valves. IMO's design guidelines go further: MSC.1/Circ.1430/Rev.3 asks for release stations in the valve room and in a continuously manned control station or safety centre, for systems installed from 2024. Older approved systems may stay in service while they remain serviceable, so many ferries still rely on the valve room.
How much does remote drencher release cost?+
EMSA's FIRESAFE II study estimated about €101,000 over the life of a new standard ro-pax and €114,000 for an existing one. That passed its limit of €7M per fatality averted on standard and passenger-focused ferries, but failed on cargo-focused ro-pax ships, which carry few passengers and much of their cargo on weather decks.
Why did Lisco Gloria's drencher fail after a bridge release?+
The master started the system from the bridge and the section valves opened, but the pump control was most probably set to manual, so no water reached the deck. The bridge did not learn why. Current IMO guidelines ask for remote indication of pump running, manifold pressure and valve position so that a failed release is visible.
Should a car-deck drencher release automatically?+
IMO's guidelines allow it, with flame and smoke detection, colour CCTV and release when two detectors activate, and manual control must remain. EMSA's FIRESAFE project group had concerns: automatic release of large water quantities could cause stability problems, and a false alarm would soak cargo. It wanted manual remote control retained for proactive use, such as cooling a deck section.
Continue the thread

Can Crews Find the Right Drencher in Smoke?
Not reliably. Urd's crew picked the section from memory; on Norman Atlantic, deck 3's valves were opened for a deck 4 fire. SOLAS 2026 now sets signage.

How Often Must a Car-Deck Drencher Be Tested?
IMO's Circ.1432 sets weekly, monthly, yearly and five-yearly drencher checks. In DNV GL's 2016 review, every drencher that missed the fire lost the ship.
Lisco Gloria: The Drencher That Gave No Water
The 2010 Lisco Gloria fire was detected within minutes and the drencher started — it delivered no water, and a 199 m DFDS ro-pax became a total loss.

PCTC Drencher Zoning and Fixed-First
Drenchers deliver 5–15 L/min/m² by deck height. Whether 'Fixed First' suppresses or floods a car deck depends on how precisely detection zones it.

What Should a Car-Carrier Fire Drill Test?
Whether the fixed system goes in within 15 minutes. New VCSF guidelines swap the routine monthly drill for six fire scenarios of rising severity.
The First Ten Minutes After an EV Alarm
Detection buys time only if the crew knows what to do with it. On a vehicle carrier the decisive variable isn't the alarm — it's the rehearsed response.