Should a Car Deck Detect Hydrogen Fluoride?

By Vignesh Durai · · 4 min read

Yes, but not for early warning. On a vented deck HF arrives late and diluted; its job is telling crews when air is lethal and when re-entry is safe.

Yes, but not as the early warning. A failing lithium-ion cell does release hydrogen fluoride (HF) at its first vent, in a small burst before thermal runaway takes hold. On a ventilated car deck, though, that burst reaches a deck-mounted sensor diluted and late, after solvent vapour, hydrogen and heat. HF sensing earns its place on a car deck as a crew-protection and re-entry instrument: it tells responders when the air will kill them and when it is safe to go back in.

20–200 mg/Wh
HF measured from lithium-ion battery fires, about 2–20 kg for a 100 kWh pack (Larsson et al., 2017)
30 ppm
HF level immediately dangerous to life or health (IDLH); 10-minute lethal value about 170 ppm
+35%
Rise in peak HF production rate when water mist was applied; total HF unchanged

Where HF comes from, and when

From the electrolyte's fluorine salt, in two pulses. Lithium-ion electrolyte carries lithium hexafluorophosphate (LiPF₆). Heated, it breaks down towards phosphorus pentafluoride, which reacts with moisture to form phosphoryl fluoride (POF₃) and HF. Researchers at KAUST reported in May 2026 that both NMC and LFP cells released a small burst of HF during initial safety venting, followed by a much larger release once thermal runaway had started. Larsson and colleagues found HF production in battery fires correlated with the heat-release rate, 'although somewhat delayed', at 20–200 mg per watt-hour of nominal capacity, with 15–22 mg/Wh of POF₃ in some tests.

Water changes the rate, not the total. In Larsson's tests, applying water mist raised the peak HF production rate by 35% without significantly changing the total released. On a ship that matters during cooling: a drencher or boundary-cooling attack can produce a short spike in HF just as crew are working close to the fire.

Why a deck sensor will not give early warning

Because the early HF signal exists at the cell, not across the deck. KAUST's prototype placed a tunable diode laser absorption sensor directly above a cell's safety vent and measured HF during initial venting at concentrations 'orders of magnitude above the level that is immediately dangerous to life and health'. That is a strong in-pack signal. By the time the same small burst has left a sealed traction pack and mixed into a mechanically ventilated deck, it has been diluted by orders of magnitude, and HF is a reactive, 'sticky' gas that adsorbs onto surfaces on the way.

Earlier, more mobile signals arrive first. Electrolyte-solvent vapour leads the sequence, hydrogen and carbon monoxide follow, and per-vehicle heat rises with them. EMSA's FIRESAFE II work also showed that deck ventilation can both delay a detection signal and move it away from its source. A deck-level HF sensor that alarms has therefore confirmed a fire already well established somewhere on the deck; it has not warned of one.

What HF sensing is actually for

Protecting the people who have to go near the fire. A 100 kWh pack can release on the order of 2–20 kg of HF, against an IDLH of 30 ppm and a ten-minute lethal (AEGL-3) value of about 170 ppm. Those are small numbers against kilogram-scale releases in an enclosed vehicle deck. CHIRP Maritime's 2026 guidance for ro-pax crews asks for gas detection 'including HF sensors' and for respiratory protection on re-entry, and stresses conservative re-entry because cells can fail again hours or days after apparent suppression.

That gives HF readings three uses: setting the boundary of the hazard zone during the response, confirming when a space can be entered without breathing apparatus, and monitoring the deck during the long cooling period when reignition and water-driven HF spikes are most likely. HF also dissolves readily into firefighting water, forming hydrofluoric acid, so the same readings help judge the hazard in contaminated runoff.

What HF sensors can and cannot do

They measure low concentrations well and need care to stay honest. Common electrochemical HF sensors cover 0–10 ppm, a range built for occupational exposure; in a fire they will saturate long before lethal levels, so the range has to match the purpose. Published datasheets give response times in the tens of seconds (t62.5 around 29 s, T90 under 50 s) and sensor lives of about two years. They cross-read other acid gases: hydrogen chloride is used as a surrogate calibration gas at around 37% cross-sensitivity, and burning plastics and cable insulation in an ordinary car fire produce HCl, so a reading is an acid-gas reading first.

HF also sticks to the sampling path. Manufacturers recommend PTFE or HDPE tubing, because HF adsorbs into other tubing walls and readings lag or fall short. On a car deck that means short sample paths, the right materials and calibration under realistic humidity and salt exposure. A portable multi-gas detector with an HF channel, carried by the re-entry team, is often more useful than a fixed head deep in the deck.

What to specify

Split the jobs. Early warning should come from signals that lead the sequence: electrolyte vapour, hydrogen and per-vehicle temperature. HF should be specified for personnel protection: portable HF channels for responders, and fixed HF measurement where crews enter the space and where exhaust leaves it, with ranges chosen for both exposure limits and fire conditions. Treat an HF reading as an answer to 'is this air survivable?', never as the answer to 'is a car starting to fail?'.

Conclusion

How RoRoSAFE helps

HF tells a crew how dangerous a burning deck has become; it cannot tell them which car started it. RoRoSAFE's early warning comes from the signals that lead: infrared thermal and battery-vent electrolyte-vapour sensing under each parked vehicle, with alerts before visible smoke that name the deck and bay. That leaves HF instruments to do what they do best: protect the people who respond and decide when they can re-enter.

Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access

Sources

  • 1. Larsson, F., Andersson, P., Blomqvist, P., Mellander, B.-E. — 'Toxic fluoride gas emissions from lithium-ion battery fires', Scientific Reports 7:10018 (2017), doi:10.1038/s41598-017-09784-z (open access, read): 20–200 mg/Wh HF; 15–22 mg/Wh POF₃ in some tests; HF production correlated with heat-release rate, 'although somewhat delayed'; water mist raised the peak HF production rate by 35% with no significant change in total; IDLH 30 ppm (0.025 g/m³); 10-minute AEGL-3 ≈170 ppm; risk of later gas explosion if vented gas is not immediately ignited.
  • 2. KAUST Physical Science and Engineering — 'Gas detector flags early battery failure' (12 May 2026): TDLAS sensor above the cell safety vent; NMC and LFP cells released small HF bursts during initial venting followed by larger releases at thermal runaway; concentrations orders of magnitude above IDLH; aim of a closed-loop in-pack warning system.
  • 3. CHIRP Maritime — 'Electric Vehicles on Roll-On and Roll-Off Passenger Ferries: Capability and Preparedness' (22 April 2026): continuous monitoring including 'gas detection (including HF sensors)'; respiratory protection for re-entry; conservative re-entry; cells failing hours or days later.
  • 4. HF sensor datasheets — Sensidyne SensAir HF 0–10 ppm (t62.5 ≈29 s); Honeywell Midas HF cartridge (≈24-month life, HCl as span gas at ≈37% cross-interference, PTFE/HDPE tubing recommended, H₂S cross-sensitivity); SGX and Winsen HF modules.
  • 5. Sequence and deck constraints as set out in this site's articles on the H₂/CO/CO₂ gas signature and electrolyte vapour, and EMSA FIRESAFE II on ventilation delaying and displacing detection.
Frequently asked

Questions, answered

Do lithium-ion battery fires release hydrogen fluoride?+

Yes. The fluorine salt in the electrolyte breaks down when heated, releasing hydrogen fluoride and phosphoryl fluoride. Tests have measured 20–200 mg of HF per watt-hour of battery capacity, which for a 100 kWh electric-vehicle pack is on the order of 2–20 kg. A small burst can appear at the first vent, with much more once thermal runaway starts.

Can HF detection give early warning of an EV fire on a ship?+

Not at deck level. A sensor placed directly at a cell's vent can see HF early, but on a ventilated vehicle deck the gas is diluted and absorbed on surfaces before it reaches a sensor, and solvent vapour, hydrogen and heat arrive first. Deck HF sensors are best used to protect responders and judge when re-entry is safe.

What concentration of hydrogen fluoride is dangerous?+

The level immediately dangerous to life or health is 30 ppm, and the ten-minute lethal value (AEGL-3) is about 170 ppm. Occupational limits are far lower, in the low single ppm. Because a single EV battery fire can release kilograms of HF, an enclosed vehicle deck can exceed these levels quickly, which is why responders wear breathing apparatus.

Does firefighting water change the HF hazard?+

It changes the timing. In laboratory battery fires, applying water mist raised the peak rate of HF production by about 35% without changing the total released. HF also dissolves into water to form hydrofluoric acid, so firefighting runoff from an EV fire needs to be treated as contaminated and handled carefully.

Related reading

Continue the thread

SensingChemistry
Sep 9, 2026 · 4 min read

H₂, CO, CO₂: The Thermal-Runaway Signature

The order matters more than the shortlist. Solvent vapour beats H₂ by about fifteen minutes — and LFP and NMC invert which gas dominates.

By Vignesh DuraiRead
SensingPre-Detection
Jul 27, 2026 · 3 min read

Can Electrolyte Vapour Warn Before Fire?

A failing lithium cell vents electrolyte-solvent vapour — DMC boils near 90°C — before any combustion gas or heat. That VOC is the earliest signature.

By Vignesh DuraiRead
RoPaxEV
Oct 7, 2026 · 4 min read

What Does CHIRP Tell Ferry Crews on EV Fires?

CHIRP's 2026 ro-pax guidance says plan for consequence: treat a failing EV battery as a gas release before a fire, and never approach early signs.

By Vignesh DuraiRead
SafetyEV
Jul 1, 2026 · 3 min read

What's the Pollution Tail of an EV Deck Fire?

A long one. A single 100 kWh EV pack can vent 2–20 kg of hydrogen fluoride, and the firewater runoff carries HF, heavy metals and PFAS foam.

By Vignesh DuraiRead
SensingSOLAS
Jul 21, 2026 · 5 min read

Does Deck Ventilation Delay Fire Detection?

Yes. SOLAS II-2/20 mandates continuous ventilation on closed vehicle decks, and that airflow dilutes smoke and off-gas before detectors see it.

By Vignesh DuraiRead
R&DRegulation
Aug 24, 2026 · 4 min read

FIRESAFE II: Open-Deck Detection Lessons

EMSA's 2018 study full-scale tested two detection technologies, not five, and named ventilation as what both delays and displaces an alarm.

By Vignesh DuraiRead
SensingChemistry
Sep 25, 2026 · 2 min read

The Four Stages of Li-Ion Thermal Runaway

Li-ion runaway moves from SEI breakdown near 80–120 °C through venting to fire. Useful detection works in the venting window, before smoke and flame.

By Vignesh DuraiRead
SensingDetection
Aug 5, 2026 · 4 min read

How Fast Does a Gas Sensor Drift at Sea?

Electrochemical cells can lose up to 20% of sensitivity a year. On a vehicle deck, the threshold you set at commissioning is not the one you have later.

By Vignesh DuraiRead