Can a Car Carrier's Fire Main Feed an EV Fire?

For one car, easily: an EV fire takes about 10 m³ and SOLAS asks for up to 180 m³/h of fire-pump capacity. Reach, run time and drainage are the limits.
For one car, easily. The UK MCA puts the water needed for an EV fire at around 10,000 litres. SOLAS never requires a cargo ship's fire pumps to total more than 180 m³/h; at that rate, 10,000 litres is about three minutes of pumping. The fire main is rarely what runs out. Getting water onto the pack, keeping it flowing for hours and getting it off the deck are the limits.
That matters because most car carriers fight a deck fire with CO2, and the fire main is what the crew has for everything CO2 does not do: boundary cooling, a first attack before the space is sealed, and cooling after a reignition. Ro-pax ferries add a drencher, which on some ships can be fed from the fire main if its own pump fails. For a superintendent or a class surveyor, the useful question is not whether the pumps meet the rule but what the rule was sized for.
What does SOLAS require of a fire main?
Two pumps, a modest total flow and enough pressure for two jets anywhere on a vehicle deck. SOLAS II-2/10 requires at least two independently driven fire pumps on a cargo ship of 1,000 GT and over. Together they must deliver four-thirds of the bilge-pump quantity for a passenger ship of the same size, but the required total need not exceed 180 m³/h, a ceiling that applies to cargo ships generally, with container ships stacking five or more tiers on deck treated separately. Each pump must give at least 80% of the total divided by the minimum number of pumps, never less than 25 m³/h, and must be able to supply two jets on its own.
With both pumps running, every hydrant on a cargo ship of 6,000 GT and over must hold at least 0.27 N/mm² (about 2.7 bar). For ro-ro and vehicle spaces, the hydrants must be placed so that two jets, each from a single length of hose, reach any part of the space. Standard nozzles are 12, 16 and 19 mm. The emergency fire pump, which must sit outside the machinery space, must deliver at least 40% of the required total and not less than 25 m³/h on cargo ships of 2,000 GT and over. On a ship at the 180 m³/h ceiling, 40% is 72 m³/h. MSC.1/Circ.1314 counts two jets at not less than 25 m³/h between them.
How much water does an EV fire take?
More than a petrol car, and over longer, but small against the pumps. The UK's MGN 653 says a conventionally fuelled vehicle needs about 4,000 litres to suppress a fire, while an electric vehicle can need around 10,000 litres, depending on battery size and how the water is applied. It adds that a pressurised drencher may not meet an EV's suppression needs and recommends water monitors where available. Our technical article on EV fire size explains why: the peak heat release is similar, but the battery burns longer and can reignite.
Road fire services report much larger totals for crashed EVs. The NTSB's 2020 safety report on lithium-ion battery fires describes one Tesla fire in Lake Forest, California, where firefighters applied more than 20,000 US gallons, about 76 m³, over at least two hours. The battery cooled only once the car was lifted so water could reach the pack. Even 76 m³ is under half an hour of a 180 m³/h fire main. The pumps were not the constraint; access to the battery was.
How far does the fire main go with two hoses?
Further than the crew can. A 19 mm nozzle at 0.27 N/mm² discharges roughly 380 litres a minute, about 23 m³/h, so the two jets the rule asks for draw around 45 m³/h. That is a quarter of the 180 m³/h cap. The fire main can keep those jets running for as long as the sea chest stays submerged.
The people holding them are the limit. Each jet needs a hose team in breathing apparatus, on a deck between cars parked about 30 cm apart, in smoke, with an EV pack under the floor that the jet cannot reach. Our blog on hoses at car fires covers what a hand-held jet can achieve, and our post on crew size covers why a crew of about 22 cannot keep two teams at a deck fire for hours.
What if the fire main must feed a drencher?
Then it falls short. Some ro-pax ferries can cross-connect the fire main to the drencher, bypassing the drencher pump. That was the fallback the Lisco Gloria's crew never tried in 2010, when the drencher pump did not run. The fixed system's demand is of a different order. Our drencher-zoning article works through a 32 m-wide deck split into 20 m sections: at 5 L/min/m², the density for decks up to 2.5 m high, the design release of two adjacent sections takes about 6.4 m³ a minute, or roughly 384 m³/h. That is more than double the most SOLAS requires of a cargo ship's fire pumps, 180 m³/h. Passenger ships are sized differently, so the gap depends on the ship.
A cross-connect can therefore keep one section wet, or a reduced density over two, while the drencher pump is restored. It cannot reproduce the design release. A fire plan that lists the cross-connect as the backup should say what it delivers.
What limits how long the water can run?
Where the water goes, and what powers the pumps. Water put onto a car deck stays there unless scuppers and freeing ports remove it, and water high in the ship destroys stability. In 2006, the Al Salam Boccaccio 98's crew fought a car-deck fire while blocked scuppers held the water, and the ship capsized with the loss of 1,031 of the 1,418 aboard. At 180 m³/h, four hours of continuous use would put 720 tonnes of water aboard. A fire main is a supply without a meter; the drains are the meter.
The rules have started to size the drains to the water. For new ro-pax ships, MSC.550(108) asks for drainage able to take 125% of the capacity of the weather-deck monitors and hoses. France's DGAMPA recommends scuppers sized above the combined capacity of the water-spray pumps and required hoses. The power supply matters too. IMO's casualty lessons include a ro-pax engine-room fire in which fire-main pressure was lost intermittently because the emergency fire pump's control cables ran through the burning space. If the main pumps are lost, a ship at the 180 m³/h ceiling still has at least 72 m³/h from the emergency pump, about three 19 mm jets by our calculation; at the 25 m³/h minimum it is closer to one.
What should an owner check on the fire main?
- Installed fire-pump capacity and pressure at the highest and farthest hydrant on each vehicle deck, with two pumps and two jets running.
- Whether two jets, each from a single hose length, genuinely reach every lane with the deck loaded, not only when empty.
- What the drencher cross-connect delivers in m³/h, how many sections it can feed, and who opens it.
- Measured scupper and freeing-port capacity with cargo and lashings in place, and a list angle at which water application stops.
- Where the emergency fire pump's power and control cables run, and whether a deck or engine-room fire can cut them.
- How long boundary cooling can run on the available crew, with breathing-apparatus changes planned.
How RoRoSAFE helps
A fire main can feed a single burning car; what it cannot do is reach a pack under the floor or cool a deck of them for hours without flooding the ship. The earlier a failing vehicle is found, the less water the fight needs. RoRoSAFE watches each parked vehicle with infrared thermal and battery-vent gas sensing, alerting bridge and shore by deck and bay before visible smoke. It complements SOLAS systems and holds no class type approval yet.
Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access
Sources
- 1. IMO — SOLAS Chapter II-2, Regulation 10 (Fire fighting), as published by the UK Maritime and Coastguard Agency: two independently driven fire pumps on cargo ships of 1,000 GT and over; total capacity four-thirds of the bilge quantity, capped at 180 m³/h; each pump at least 80% of its share and not less than 25 m³/h; hydrant pressures (cargo 0.27/0.25 N/mm², passenger 0.40/0.30 N/mm²); two jets each from a single hose length to reach any part of a ro-ro or vehicle space; nozzles 12, 16 and 19 mm.
- 2. IACS — Unified Interpretation SC270 (Rev.1, December 2015), on container ships with five or more tiers on deck, quoting the general rules: SOLAS II-2/10.2.2.4.1.2, 180 m³/h limit on required fire-pump capacity; FSS Code ch. 12, 2.2.1.1, emergency fire pump at least 40% of total required capacity and not less than 25 m³/h for cargo ships of 2,000 GT and over.
- 3. IMO — MSC.1/Circ.1314, 10 June 2009, application of SOLAS II-2/10 and FSS Code chapter 12 to emergency fire pump capacity: where the emergency pump also supplies a fixed water system for the machinery space, two jets are added at not less than 25 m³/h; minimum pressure 0.27 N/mm².
- 4. UK Maritime and Coastguard Agency — MGN 653 (M) Amendment 1, §§3.12–3.13: about 4,000 litres for a conventionally fuelled vehicle fire and around 10,000 litres for an EV; pressurised drencher may not meet EV needs; water monitors recommended.
- 5. NTSB — Safety Report SR-20/01, 'Safety Risks to Emergency Responders from Lithium-Ion Battery Fires in Electric Vehicles' (2020): Lake Forest, California, fire with more than 20,000 gallons applied over at least two hours; battery cooled only when the vehicle was raised.
- 6. IMO — Lessons learned from casualties, consolidated 'Fire – Explosion': ro-pax auxiliary engine-room fire with intermittent loss of fire-main pressure after the emergency pump's control cables were damaged.
- 7. Drencher demand: two 20 m sections of a 32 m-wide deck at 5 L/min/m², about 6.4 m³/min. As worked in RoRoSAFE's technical article 'PCTC Drencher Zoning and Fixed-First'.
- 8. BSU (Germany) — Lisco Gloria fire, 2010: drencher pump did not run; untried cross-connect to the fire main. As covered in RoRoSAFE's case study 'Lisco Gloria: The Drencher That Gave No Water'.
- 9. Al Salam Boccaccio 98, 2006: firefighting water retained by blocked scuppers; 1,031 of 1,418 lost. As covered in RoRoSAFE's case study 'Al Salam Boccaccio 98: Sunk by Firewater'.
- 10. IMO — Resolution MSC.550(108): weather-deck drainage for 125% of monitor and hose capacity on new ro-pax ships; DGAMPA (France) recommendation on scupper sizing. As covered in RoRoSAFE's posts on weather-deck stowage and France's EV guidelines.
Questions, answered
How much water does a ship's fire main deliver?+
SOLAS II-2/10 requires at least two independently driven fire pumps on a cargo ship of 1,000 GT and over. Their required combined capacity is four-thirds of a comparable passenger ship's bilge-pump quantity, with no more than 180 m³/h required. Each pump must give at least 25 m³/h, and hydrants on ships of 6,000 GT and over must hold 0.27 N/mm² with two pumps running.
How much water does an electric car fire need?+
The UK MCA's MGN 653 puts it at around 10,000 litres, against about 4,000 litres for a petrol or diesel car, depending on battery size and how water is applied. Road fires can take far more: the NTSB described one crashed Tesla that took more than 20,000 gallons over two hours before the pack, reached from below, cooled.
Can a fire main supply a ro-ro drencher?+
Only in part. Some ferries can cross-connect the fire main to the drencher if its pump fails, as Lisco Gloria could have in 2010. But two drencher sections on a 32 m-wide deck at 5 L/min/m² need about 384 m³/h, more than double the 180 m³/h cap on a cargo ship's required fire pumps. A cross-connect keeps one section wet; it cannot match the design release.
Why can't crews just keep pumping water onto a car-deck fire?+
Because water that stays on a deck high in the ship destroys stability. At 180 m³/h, four hours of pumping puts about 720 tonnes aboard. The Al Salam Boccaccio 98 capsized in 2006 after blocked scuppers held its firefighting water. Drainage capacity, not pump capacity, sets how long water can run.
Continue the thread

PCTC Drencher Zoning and Fixed-First
Drenchers deliver 5–15 L/min/m² by deck height. Whether 'Fixed First' suppresses or floods a car deck depends on how precisely detection zones it.
Lisco Gloria: The Drencher That Gave No Water
The 2010 Lisco Gloria fire was detected within minutes and the drencher started — it delivered no water, and a 199 m DFDS ro-pax became a total loss.

Al Salam Boccaccio 98: Sunk by Firewater
A car-deck fire the crew fought. Blocked scuppers held the water, free surface took the stability, and 1,031 of 1,418 aboard were lost.

Can a Hose Put Out a Car Fire on Deck?
Only early. A hose can halve the heat reaching the next car if a crew gets there in minutes; on a smoke-filled deck or an EV pack, it rarely can.
Does an EV Fire Burn Bigger Than a Petrol Car?
Not at its peak: full-scale tests put EV and petrol car fires in the same 4–7 MW band. A battery fire grows slower, burns longer and can reignite.

Is a 22-Person Crew Enough for a Car-Deck Fire?
Enough to release CO₂ fast, not to fight the fire by hand. Car carriers sail with about 22 crew for 13 decks, so time, not headcount, decides it.