Pyxis: Fire Out, Chief Engineer Lost to CO₂

Pyxis flooded its burning car deck with CO₂ 22 minutes after the alarm in 2008. The chief engineer, missing at roll call, died of the gas.
Pyxis is a car-carrier fire the CO₂ system won and the crew lost a man. On 14 October 2008 a fire in one car on deck 10 tripped the smoke alarm at 09:48. CO₂ went in about 22 minutes later and kept the fire in the hold. The chief engineer, missing at roll call, died of CO₂ on deck 7.
Japan's Transport Safety Board investigated as a substantially interested state, since the ship was Panama-flagged but the chief engineer was Japanese, and published report MA2011-10 in October 2011. It is an unusually complete record: a bridge voice transcript, the detector layout, CO₂ release times and the route the chief engineer probably took. Its lessons sit in the gap between putting a fire out and accounting for the crew.
What happened
A routine transpacific voyage, a fire nobody had seen on patrol, and a decision to seal and flood within half an hour. Pyxis left Mikawa, Japan, at about 18:40 on 12 October with 3,900 new cars for Portland, Oregon, and 22 people aboard. Deck crew were inspecting lashings on the lower decks, engineers were overhauling valves, and two able seamen had patrolled the car decks at 03:00 and 07:00 without finding anything.
- 09:48:37 — the smoke-sampling detection system alarms on the bridge: accumulator 54, Zone F, deck 11, port side.
- 09:52:40 — the third officer, having opened the fire door of deck 10, reports a fire: he saw a bright yellow light.
- 09:53:27 — general alarm. The PA then announces a fire on deck 11, hold 3.
- 09:59:30 — insulation alarm on the car-deck lighting circuit; its breaker is shut off, cutting the car-deck lighting.
- About 10:04–10:06 — all crew ordered to the muster station for a CO₂ release. At 10:08 the chief engineer is reported missing.
- About 10:10 — CO₂ into Zone F. When detectors alarm in Zones E and D, the master releases there too, stopping at 10:25 with about 60% of 35 t used.
- 10:20 — fire alarm in the accommodation: smoke from a boat-deck ventilator has been drawn into the air-conditioning intake.
- 11:07 — a second release into Zones D, E and F, as the master is not confident the fire is out. All CO₂ is gone by 11:16. The ship turns back for Japan.
- 15 October, 10:20 — a Japan Coast Guard special rescue team, aboard since 07:58, ventilates the decks and confirms the fire is out. At 10:45 it finds the chief engineer's body on deck 7.
- 16 October, 07:30 — Pyxis berths back at Mikawa.
Where did the fire start, and why is the cause unknown?
In the engine bay of car 10-07 on the port side of deck 10, by a mechanism the JTSB could not establish. The cars were petrol models carrying 3 to 15 litres of fuel each, stowed about 30 cm bumper to bumper and 10 cm door to door, with ignition keys removed. Car 10-07 was the most severely burnt, its neighbours were scorched on the sides facing it, and cars on decks 11 and 12 were damaged by heat from below.
The investigators ruled out the fuel system, since the tank still held fuel and no pipe connector had come apart, and the exhaust, which showed no sign of overheating. They judged the ship's lighting circuit less probable, as its insulation alarm came 11 minutes after the fire alarm, and smoking less probable. Melting on the car's main ground-wire terminal could not be reproduced in tests and was attributed to short circuits after the fire began. The JTSB noted that a parked car with its key removed still has live circuits, and that a short too small to trip a breaker can heat a cable until its insulation burns. It could not show that this happened, so the cause remains undetermined.
What did the detection system see?
Smoke on the deck above the fire. Pyxis had an aspirating smoke-sampling system with 122 accumulators, one for every two decks, mounted on the floor of the upper deck of each pair; decks 2, 4, 7, 10 and 12 had none of their own. Smoke from deck 10 reached the accumulator on deck 11 through ventilation openings, so the alarm and the PA both named deck 11. The system worked as designed, with a measured transport time of about 57 seconds against ClassNK's 3-minute limit.
The mismatch shaped the first minutes. The third officer, taking the elevator, which stopped at deck 10, found the fire there. The master went to deck 11 with a portable extinguisher, found no flames but thick, irritating smoke, and turned back. Within about four minutes of the alarm the fire was already visible. The JTSB also found that neither fire alarms nor PA announcements could be heard on the car decks, and two seamen went down to deck 6 in person to tell the crew inspecting lashings there.
Did the CO₂ work?
For the ship, yes. The ventilation fans were normally stopped after departure. The master had the dampers closed, sealed the hold and released CO₂, and the JTSB credits that with confining the damage to the cargo hold. But smoke reached Zones E and D although their fire doors and the gastight ramp doors were probably closed, and the JTSB could not determine how. The master flooded those zones as well, then used the rest of the charge in a second release because he could not confirm the fire was out.
By 11:16, about 90 minutes after the alarm and 340 nautical miles from Japan, the ship had no CO₂ left. The crew cooled the boat deck above deck 13 with water, and the fire was confirmed out only the next morning. The damage shows how hot it got: a beam at frame 70 was melted down by up to 220 mm, deck 10's headroom dropped from 2,700 mm to about 2,480 mm where deck 11 sagged, and nearly all the damaged cars were scrapped.
How did the chief engineer die?
In the zone that was flooded, with no light, no radio and an empty escape set. The engine control room was his station in a fire. When the crew were ordered to muster, he told the first engineer to go ahead because he would be the last to leave. He left wearing an emergency escape breathing device but without a torch, and without the radio the muster list required him to carry. He did not take the signed escape route through the steering-gear room. The JTSB thought it possible that he climbed the engine-room stairs to deck 6 and a vertical ladder to deck 7, avoiding the tightly packed hold, and found that deck dark after the lighting breaker was shut. A third route through the port bunker station was unusable: its watertight door was locked from the deck 6 side.
The master knew the chief engineer was missing but, told he meant to leave last, believed he was still in the engine control room, away from Zone F. CO₂ then went into Zone D, where deck 7 lies. The chief engineer was found between a car and the engine-room bulkhead with his breathing device empty, dead of CO₂ intoxication. The JTSB found no record of CO₂ release drills simulating a real emergency, judged that a radio might have let him be found and rescued, and asked the managers to set procedures for confirming that a space is clear before CO₂ goes in.
What does Pyxis teach car-carrier operators?
- Know which deck is burning. A deck without its own detector is reported one deck away; on Pyxis that sent the master to the wrong deck first.
- Make roll call a gate, not a formality. Before CO₂ goes into a zone, anyone missing should be located or that zone confirmed clear, as the JTSB asked.
- Make the alarm audible where people work. Neither the fire alarm nor the PA reached the car decks while crew were inspecting lashings there.
- Carry the kit the muster list names. Lighting may be cut to stop electrical fires, so a torch and radio matter as much as the escape set.
- Keep every escape route openable from both sides, and drill the signed route rather than the shortest one.
- Plan for the CO₂ running out. Pyxis used its whole 35 t charge within 90 minutes and still could not confirm the fire was out.
How RoRoSAFE helps
Pyxis's alarm came from the deck above the burning car, and by the time crew arrived the fire was visible. RoRoSAFE places infrared thermal sensing beneath each parked vehicle, with battery-vent gas sensing for EVs, and sends tiered bridge and shore alerts naming the deck and bay before visible smoke. So the master knows sooner where to send people and which zone to flood. It complements the CO₂ system and holds no class type approval yet.
Pilot: one deck · installed alongside the berth · no drydock · 6 months of dashboard access
Sources
Questions, answered
What happened on the car carrier Pyxis in 2008?+
On 14 October 2008, 340 nautical miles east of Japan, a fire broke out in the engine bay of one car on deck 10 of the vehicles carrier Pyxis, which was carrying 3,900 new cars. The master sealed the hold and released CO₂ about 22 minutes after the first alarm, and the fire stayed in the cargo hold. The chief engineer died of CO₂ intoxication on deck 7.
Why did the Pyxis chief engineer die?+
He stayed in the engine control room to be last out, then left wearing an escape breathing device but without a torch or the radio the muster list required. He did not use the signed escape route and entered deck 7, which was dark. The master believed he was still in the engine control room and released CO₂ into the zone containing deck 7.
What caused the Pyxis fire?+
Japan's Transport Safety Board found the fire probably began in the engine bay of one petrol car on deck 10. It ruled out the fuel and exhaust systems and judged the ship's lighting circuit and smoking less probable. It could not establish whether the car's electrical system started the fire, so the cause remains undetermined.
Why did the Pyxis alarm point to the wrong deck?+
The smoke-sampling system had one accumulator for every two decks, mounted on the upper deck of each pair, and deck 10 had none of its own. Smoke from the fire on deck 10 reached the accumulator on deck 11, so the alarm and the PA announcement named deck 11 while the burning car was one deck below.
Continue the thread

Honor: Thirty-Seven Minutes to CO₂
The 2017 Honor fire is the fastest documented CO₂ release on a car carrier — alarm 0302, gas 0339. It emptied the ship's CO₂ and still cost $700,000.
Aspirating vs Point Smoke on Vehicle Decks
Point detectors alarm only once diluted smoke reaches the deckhead; aspirating (ASD) systems sample air continuously and trip far earlier.

Should Car Carriers Carry Twice the CO₂?
IUMI says PCTC CO₂ capacity should at least double. The rules size it for one shot, and IMO's EV rules are years off. What a second charge buys owners.

How Long Must a CO₂-Flooded Space Stay Sealed?
Until boundaries reach ambient — hours to days. The FSS Code sets no hold time, NFPA 12 sets 20 minutes, and re-entry at 3 hours has re-ignited fires.

What Should a Car-Carrier Fire Drill Test?
Whether the fixed system goes in within 15 minutes. New VCSF guidelines swap the routine monthly drill for six fire scenarios of rising severity.

What Does a VDR Record of a Car-Deck Fire?
Less than investigators need. A VDR logs bridge fire alarms, door status and audio, not the fire panel's full history, and most of it stops in a blackout.